2-25. E: 86. High pressure switch error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 86
Detective actuator
Outdoor unit main PCB
When pressure switch open is detected in 10 seconds
after the power is turned on.
High pressure switch
Forecast of cause
High pressure switch connector disconnection or open
High pressure switch characteristics failure
Main PCB failure
Check point 1. Check the high pressure switch connection state
•
Check connector and wiring connection state.
•
Check if cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Check the high pressure switch characteristics
•
Check switch characteristics.
For the characteristics of the high pressure switch, refer to below.
↓
Check point 3. Replace main PCB
Change main PCB and check operation again.
↓
End
• Type of contact
C
H
Pressure
• Characteristics of pressure switch
Pressure switch 1
Contact: Short → Open
4.2±0.1 MPa
Contact: Open → Short
3.2±0.15 MPa
36/45 model: P770
2-25. E: 86. High pressure switch error (Outdoor unit)
- (03-30) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABYG36KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Page 40: ......
Page 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Page 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Page 106: ......
Page 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...