1-5. Compressor frequency limitation by outdoor temperature
The minimum compressor frequency is limited by outdoor temperature as below.
•
Cooling/Dry mode
F zone
13°C
E zone
7°C
D zone
°C
C zone
B zone
A zone
-5
2
°C
-10°C
G zone
21°C
J zone
50°C
K zone
52°C
H zone
31°C
I zone
46°C
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOYG36KRTA
A zone
55 rps
B zone
52 rps
C zone
47 rps
D zone
39 rps
E zone
33 rps
F zone
25 rps
G zone
18 rps
H zone
20 rps
I zone
20 rps
J zone
21 rps
K zone
24 rps
AOYG45KRTA
A zone
50 rps
B zone
47 rps
C zone
40 rps
D zone
30 rps
E zone
22 rps
F zone
20 rps
G zone
16 rps
H zone
16 rps
I zone
17 rps
J zone
23 rps
K zone
28 rps
1-5. Compressor frequency limitation by outdoor temperature
- (04-5) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for ABYG36KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Page 40: ......
Page 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Page 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Page 106: ......
Page 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...