8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢
Model: AOYG36KRTA
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
52°C ≤ Ta
3.5 A
3.0 A
50°C ≤ Ta < 52°C
5.5 A
5.0 A
42°C ≤ Ta < 50°C
6.0 A
5.5 A
2°C ≤ Ta < 42°C
7.5 A
7.0 A
Ta < 2°C
8.5 A
8.0 A
Heating
20°C ≤ Ta
5.5 A
5.0 A
16°C ≤ Ta < 20°C
6.0 A
5.5 A
12°C ≤ Ta < 16°C
7.0 A
6.5 A
2°C ≤ Ta < 12°C
7.5 A
7.0 A
Ta < 2°C
8.5 A
8.0 A
¢
Model: AOYG45KRTA
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
52°C ≤ Ta
4.5 A
4.0 A
50°C ≤ Ta < 52°C
5.5 A
5.0 A
46°C ≤ Ta < 50°C
6.5 A
6.0 A
42°C ≤ Ta < 46°C
7.5 A
7.0 A
2°C ≤ Ta < 42°C
8.5 A
8.0 A
Ta < 2°C
10.0 A
9.5 A
Heating
20°C ≤ Ta
6.5 A
6.0 A
16°C ≤ Ta < 20°C
7.0 A
6.5 A
12°C ≤ Ta < 16°C
8.0 A
7.5 A
2°C ≤ Ta < 12°C
8.5 A
8.0 A
Ta < 2°C
10.0 A
9.5 A
8-4. Indoor unit fan motor over temperature protection
When satisfy the following conditions, the protection works.
• After the 90 seconds from the fan operation, detect less than 300 rpm for 10 seconds.
• IPM trip protection works.
• Current overload protection works.
When detecting the above condtion, recheck the condition after 6 minutes. When count the twice,
the protection works.
•
Protection contents
Reduce the static pressure 20 Pa. When it does not dissolve even the minimum static pressure
condition, work the following operation.
– Fan motor error displayed when less than 300 rpm for 10 seconds is detected after the 90 sec-
onds from the fan operation.
– Fan stop 40 seconds when IPM trip protection works.
– Fan stop 50 seconds when corrent overload protection works.
8-3. Current release control
- (04-29) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for ABYG36KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Page 40: ......
Page 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Page 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Page 106: ......
Page 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...