2-9. E: 35. MANUAL AUTO button error (Indoor unit)
Indicator
Wired remote
controller
Error code
E: 35
Detective actuator
Indoor unit controller PCB
When the MANUAL AUTO button becomes on for
consecutive 60 or more seconds.
Indicator PCB
Manual auto switch
Forecast of cause
MANUAL AUTO button failure
Controller PCB and indicator PCB failure
Check point 1. Check the MANUAL AUTO but-
ton
If MANUAL AUTO button is disabled (on/off
switching), replace it.
•
Check if MANUAL AUTO button is
kept pressed.
•
Check On/Off switching operation
by using a meter.
↓
Check point 2. Replace main PCB and indicator PCB
If Check Point 1 does not improve the symptom, change main PCB and indicator PCB.
↓
End
2-9. E: 35. MANUAL AUTO button error (Indoor unit)
- (03-14) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABYG36KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Page 40: ......
Page 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Page 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Page 106: ......
Page 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...