2-30. E: 99. 4-way valve error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 99
Detective actuator
Indoor unit
main PCB
When the indoor heat exchanger temperature is
compared with the room temperature, and either
following condition is detected continuously two times,
the compressor stops.
Indoor heat exchanger temp. - Room temp. > 10 °C
(Cooling or Dry operation)
Indoor heat exchanger temp. - Room temp. < -10 °C
(Heating operation)
If the same operation is repeated 5 times, the
compressor stops permanently.
Heat exchanger temperature
thermistor
Room temperature thermistor
4-way valve
Forecast of cause
Air filter clogged
Connector connection failure
Thermistor failure
Coil failure
4-way valve failure
Main PCB failure
Check point 1. Check air filter condition
Check air filter dirty.
→ If the air filter dirty, clean up the air filter.
↓
Check point 2. Check connection of connector
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if thermistor cable is open.
→ Upon correcting the removed connector or mis-wiring, reset the power.
↓
Check point 3. Check each thermistor
•
Isn’t it fallen off the holder?
•
Is there a cable pinched?
Check characteristics of room thermistor and indoor unit heat exchanger thermistor.
For the thermistor resistance value, refer to
"Thermistor resistance values"
→ If defective, replace the thermistor.
↓
2-30. E: 99. 4-way valve error (Outdoor unit)
- (03-35) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABYG36KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Page 40: ......
Page 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Page 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Page 106: ......
Page 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...