3-5. Abnormal noise
Forecast of cause
Abnormal installation (indoor unit/outdoor unit)
Fan failure (indoor unit/outdoor unit)
Compressor failure (outdoor)
Diagnosis method when abnormal noise is occurred
Abnormal noise is coming from Indoor unit.
(Check and correct followings)
Abnormal noise is coming from Indoor unit.
(Check and correct followings)
↓
↓
•
Is main unit installed in stable condi-
tion?
•
Is the installation of air suction grille and
front panel normal?
•
Is main unit installed in stable condi-
tion?
•
Is fan guard installed normally?
↓
↓
•
Is fan broken or deformed?
•
Is the screw of fan loose?
•
Is there any object which obstruct the
fan rotation?
•
Is fan broken or deformed?
•
Is the screw of fan loose?
•
Is there any object which obstruct the
fan rotation?
↓
↓
End
Check if vibration noise by loose bolt or
contact noise of piping is happening.
↓
Is compressor locked?
•
Check Compressor
Refer to compressor and inverter com-
pressor in
↓
End
3-5. Abnormal noise
- (03-47) -
3. Troubleshooting without error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABYG36KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Page 40: ......
Page 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Page 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Page 106: ......
Page 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...