2-3. E: 12. Wired remote controller communication error (Indoor
unit)
Indicator
Wired remote
controller
Error code
E: 12
Detective actuator
Indoor unit
Main PCB
When the indoor unit cannot receive the signal from
Wired remote controller more than 1 minute during
normal operation.
Wired remote control
Forecast of cause
Terminal connection abnormal
Wired remote control failure
Main PCB failure
Check point 1. Check the connection of terminal
After turning off the power, check & correct the
followings.
•
Check the connection of terminal between
wired remote controller and indoor unit, and
check if there is a disconnection of the ca-
ble.
↓
Check Point 1-2 : Check Wired remote controller
and main PCB
•
If it is DC 12 V, remote controller is failure.
(Main PCB is normal)
–
Replace remote control
•
If it is DC 0 V, main PCB is failure. (Check
remote controller once again)
–
Replace main PCB
Check voltage at CN14 of main PCB
(terminal 1—3, terminal 1—2). (Power
supply to the remote controller)
Upon correcting the removed connec-
tor or mis-wiring, reset the power.
↓
End
Check Point 2 : Wire installation wrong remote
controller group setting
•
Wrong wire connection in remote controller
group (Please refer to the installation manu-
al)
•
The number of connecting indoor unit and
remote controller in one remote controller
group were less than 32 units.
↓
Check Point 2-1 : Check Indoor unit main PCB
•
Check if main PCB damage
•
Change main PCB and check the
error after setting remote controller
address
↓
End
2-3. E: 12. Wired remote controller communication error (Indoor unit)
- (03-8) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABYG36KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Page 40: ......
Page 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Page 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Page 106: ......
Page 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...