6
1. Error Messages
6-1
Error Handling
1.
Error Messages
There are five kinds of error messages displayed on the TS series:
1. Communication Error
2. Data Loading
3. Warning
4. Touch switch is active.
1.
Communication Error
When communication is not established between the TS series and a controller, or any abnormality
(noise etc.) is detected, the following messages are displayed on the TS series.
* If the above error messages are displayed on the TS series without establishing communication
between TS and PLC, test the solution of remark “1”. If the error occurs suddenly in
communication, test the solution of remark “2”.
• Comm. Error Handling: Continue
• Comm. Error Handling: Stop
Error Messages
Contents
Solution
Remarks
Time-Out
Although a request to send is given to a
controller, no answer is returned within the
specified time.
1. Check settings in the [Communication
Setting] tab window of the [Device
Connection Setting] dialog.
2. Check the cable connection.
1
3. Data may be disrupted because of
noise. Fix noise.
2
Parity
An error occurred in parity check.
1. Check the cable connection.
1
2. Data may be disrupted because of
noise. Fix noise.
2
Framing
Although the stop bit must be [1], it is
detected as [0].
1. Check settings in the [Communication
Setting] tab window of the [Device
Connection Setting] dialog.
2. Check the cables and wiring.
1
3. Data may be disrupted because of
noise. Fix noise.
2
Overrun
After one character is received, the next
character is received before internal
processing is completed.
1. Check settings in the [Communication
Setting] tab window of the [Device
Connection Setting] dialog.
1
2. Data may be disrupted because of
noise. Fix noise.
2
Check code error
The check code in the controller response
was not correct.
1. Check settings in the [Communication
Setting] tab window of the [Device
Connection Setting] dialog.
1
2. Data may be disrupted because of
noise. Fix noise.
2
Summary of Contents for MONITOUCH TS Series
Page 1: ......
Page 10: ...11 Features 2 Models and Peripheral Equipment 3 System Composition Product Outline ...
Page 43: ...2 26 6 LAN Connector TS1100i TS1070i Only Please use this page freely ...
Page 44: ...31 Mounting Procedure 2 Power Supply Cable Connection Installation ...
Page 49: ...41 Coin type Lithium Battery 2 DIP Switches Handling of TS Series Components ...
Page 57: ...4 8 2 DIP Switches Please use this page freely ...
Page 58: ...51 Before Operation 2 Main Menu Screen 3 System Menu TS Series Operations ...
Page 102: ...5 44 3 System Menu Please use this page freely ...
Page 103: ...61 Error Messages 2 Troubleshooting Error Handling ...
Page 110: ...71 Inspection and Maintenance 2 Warranty Policy Inspection and Maintenance ...
Page 114: ...7 4 2 Warranty Policy Please use this page freely ...