5 Selecting Function
5-5
FVR-C11S-EN
5
Change during operation: X = impossible,
= possible (enabled by using
),
= possible (enabled by using
)
Func-
tion
code
No.
Name
Setting range
Unit
Min.
unit
Factory
setting
Change
during
opera-
tion
User
set-
ting
H04
Retry (count)
0: No retry
1: Retry (Count is fixed to 5.)
-
-
0
H06
Cooling fan on/
off control
0: Inactive
1: Active
-
-
0
H20
PID control
(Mode select)
0: Inactive
1: Active (forward operation)
2: Active (reverse operation)
-
-
0
X
H21
(Feedback
signal select)
0: Terminal [12]
(0 to +10VDC) Input
1: Terminal [C1]
(4 to 20mADC)Input
2: Terminal [12]
(+1 to +5VDC) Input
-
-
1
X
H22
(P-gain)
0.01 to 10.0 times (1to1000%)
-
0.01
0.01
H23
(I-gain)
0.0s : Inactive
0.1 to 999s
s
0.1
0.0
H24
(D-gain)
0.00s : Inactive
0.01 to 10.0s
s
0.01
0.00
H25
(Feedback
filter)
0.0 to 60.0s
s
0.1
0.5
O: Optional Functions
Func-
tion
code
No.
Name
Setting range
Unit
Min.
unit
Factory
setting
Change
during
opera-
tion
User
set-
ting
o00
Option selection
(RS485
communication)
0: Option inactive
1: Option active
Set 0 when the optional RS485
communication unit is not used.
-
-
0
o01
Station address
1 to 31
-
-
1