2 Installation and Connection
2-7
FVR-C11S-EN
2
Table 2-3-3
Description of function F02
F02
When SW7 is set at CM
When SW7 is set at P24
0
When +24 to +27 VDC is supplied to
FWD - P24/CM, pressing the
key on the
keypad panel starts forward operation.
When +24 to +27 VDC is supplied to
REV - P24/CM, pressing the
key on the
keypad panel starts reverse operation.
When +24 to +27 VDC is supplied to both
FWD - P24/CM and REV - P24/CM, the inverter
decelerates to stop.
When FWD is short-circuited to P24/CM and the
key on the keypad panel is pressed, for-
ward operation starts.
When REV is short-circuited to P24/CM and the
key on the keypad panel is pressed, re-
verse operation starts.
When both FWD - P24/CM and REV - P24/CM
are short-circuited, the inverter decelerates to
stop.
1
When +24 to +27 VDC is supplied to
FWD - P24/CM, forward operation starts.
When +24 to +27 VDC is supplied to
REV - P24/CM, reverse operation starts.
When +24 to +27 VDC is supplied to both
FWD - P24/CM and REV - P24/CM, the inverter
decelerates to stop.
Short-circuit FWD to P24/CM for forward opera-
tion, or REV to P24/CM for reverse operation.
Short-circuiting both FWD - P24/CM and REV -
P24/CM brings the inverter to deceleration and
stop.
3) Analog input terminal (13, 12, 11, C1)
Use these terminals to connect external input
analog voltage and analog current and fre-
quency setting device (POT). For connecting
a contact to this circuit, use a twin contact for
fine current signal.
Do not use a contact for terminal 11.
CAUTION
In case P24 is short-circuited with 0V
by outer circuit when SW7 is set to P24
side, poly switch (F1) turns the power
off. To recover the power, open the
short circuit and turn the inverter off to
allow the temperature to lower.
WARNING
The STOP key is valid only when the
function has been set. Prepare
another switch for emergency stop.
When operation using an external si-
gnal terminal is selected, the operation
cannot be stopped using the STOP
key on the keypad panel.
Otherwise accidents could occur.