2-10
2 Installation and Connection
FVR-C11S-EN
2
Classifi-
cation
Terminal
symbol
Terminal name
Detailed specifications
Remarks
Analog
input
13
Power supply for
variable resistor
z
Used as power supply for frequency
setting device
(POT: 1 to 5 k
Ω
).
(+10VDC 10mADC max.)
12
Frequency setting
voltage input
z
0 to +10VDC/0 to 100%,0 to +5VDC/0
to 100% (Input impedance : 22 k
Ω
)
C1
Frequency setting
current input
z
4 to 20mADC/0 to 100%
(Input impedance : 250
Ω
)
11
Analog common
z
Common terminal for analog input
signals
Digital
input
FWD
Forward operation
/Stop command
z
Forward operation with
FWD-P24/CM ON and
deceleration-stop with
FWD-P24/CM OFF
(Switch SW7 to P24)
Decelera-
tion-stop
with
FWD-P24/
CM and
REV-P24/
CM ON
REV
Reverse
operation
/Stop command
z
Reverse operation with
REV-P24/CM ON and
deceleration-stop with
REV-P24/CM OFF
(Switch SW7 to P24)
X1
Digital input 1
z
The functions listed below can be set
by the X1 to X3 terminal functions.
Set with
functions
E01 to E03
X2
Digital input 2
X3
Digital input 3
(SS1)
(SS2)
Multistep
frequency
selection
z
Up to four steps speed operation can
be selected with SS1 and SS2
ON/OFF signals.
(BX)
Coast to stop
command
z
Inverter output is cut immediately and
the motor coasts to a stop (no alarm
output) if BX goes on.
(RST)
Alarm reset
z
The inverter releases the status held
after stop with an alarm when RST
changes from ON to OFF.
(THR)
External alarm
input
z
The inverter stops with an alarm if
THR is set to OFF.
(WE-KP)
Write-enable com-
mand for keypad
(data change al-
lowed)
z
Data rewriting for each function with
the keypad panel is rejected if WE-KP
is OFF.
z
Rewriting with keypad panel is
allowed if WE-KP is ON.