2 Installation and Connection
2-11
FVR-C11S-EN
2
Table 2-3-4 Functions of control circuit terminals
Classifi-
cation
Terminal
symbol
Terminal name
Detailed specifications
Remarks
Digital
input
(Hz/PID)
PID control cancel
z
PID control cancel with Hz/PID ON
z
PID control with Hz/PID OFF
(LE)
Link operation
selection
z
Operation based on command from
RS485 with LE ON
z
Inverter single operation with LE OFF
Output/
Input
P24/CM
Power Supply/
Digital Common
z
DC Power supply (SW7 set to P24)
(+24 to +27 VDC, 40mA max.)
z
Common terminal for digital input
signal (SW7 set to CM) (factory set-
ting)
Switching of
P24/CM ter-
minal with
switch SW7
Analog
output
FM, 11
Analog monitor
Data selected between the following
items is output with DC voltage:
z
Output frequency
z
PID feedback value
z
Output current
z
DC link circuit voltage
* Up to two analog voltmeters (input
impedance : 10 k
Ω)
can be connected.
Note:
Output waveform: An AC pulse
is output with consistent frequen-
cy and variable duty.
The average DC voltage is pro-
portional to output frequency and
output current
(frequency : 121.6 Hz).
Contact
output
30A
30B
30C
Alarm output for
any fault
If the inverter is stopped with an alarm,
the non-voltage contact signal (1SPDT)
is output
(Contact rating: 250V AC, 0.3 A, Power
factor = 0.3)
(48V DC, 0.5A for Low-voltage Directive
or 42V DC, 0.5A for UL/cUL)
* Whether an alarm is generated with an
exciting operation or non-exciting opera-
tion can be switched.
Optional
DX+
DX-
RS485 communi-
cation input/output
z
Terminal for RS485 communication
(when option board is installed)
z
DX+ : Non-inverted signal,
z
DX- : Inverted signal
Installed
on optional
board.