![Fuji Electric FVR-C11S-7EN Series Instruction Manual Download Page 36](http://html1.mh-extra.com/html/fuji-electric/fvr-c11s-7en-series/fvr-c11s-7en-series_instruction-manual_2341873036.webp)
3-1
3 Operation
FVR-C11S-EN
3
3 Operation
Table 3-2-1 General operation method
3-1 Inspection
and Prepara-
tion before
Operation
Check the following before operation:
1) Check whether the connection is correct.
For single-phase 200V series, check whether the power supply is
connected correctly to the L1/L and L2/N terminals. Also check
whether the inverter grounding terminal
G is securely connected.
2) Check for short-circuits and ground faults between terminals and be-
tween live parts.
3) Check for loose terminals, connectors, and screws.
4) Check whether the motor is separated from mechanical equipment.
5) Set switches to OFF before turning on the power so that the inverter
will not start or operate abnormally at power-on.
6) Check the following after power-on:
a) Check for alarms displayed on the keypad panel.
1. Always install the surface cover before turning on the power.
Do not remove the surface cover during conduction.
Otherwise electric shock could occur.
2. Do not operate a switch with wet hands.
Otherwise electric shock could occur.
3-2 Operation
Method
There are various operation methods. Select a method depending on
the purpose and operation specifications with reference to Chapters 4
and 5. Table 3-2-1 lists operation methods used generally.
Operation method
Frequency setting
Running command
Operation by
using keypad
panel
Built-in frequency setting
POT (VR) or UP/DOWN
key
RUN/STOP key
Operation by
using external
signal terminal
Setting by using analog
voltage, analog current,
and external POT (VR)
Contact input (switch)
z
When SW7 is set at CM
Connect external power supply and connect
terminal FWD with the (+) terminal of the
external power supply,
or connect terminal REV with the (+)
terminal of the external power supply.
z
When SW7 is set at P24
Connect terminal FWD with P24/CM or
connect terminal REV with P24/CM.
Refer to section 2-3-3.
WARNING