11-6
11.3.3 Leakage current
Table 11.1 Leakage Current of EMC Filter Built-in Type of Inverters
Input power
Inverter type
Leakage current (mA)
*1), *2)
Normal
Worst
Three-phase 400 V
FRN0002C2E-4
5.4
33.0
FRN0004C2E-4
FRN0005C2E-4
3.8
25.0
FRN0007C2E-4
FRN0011C2E-4
FRN0013C2E-4
9.6
16.0
FRN0018C2E-4
FRN0024C2E-4
18.5
29.8
FRN0030C2E-4
Single-phase 200 V
FRN0001C2E-7
8.3
8.3
FRN0002C2E-7
FRN0004C2E-7
FRN0006C2E-7
12.4
12.4
FRN0010C2E-7
4.1
8.2
FRN0012C2E-7
Note: A box (
) in the above table replaces E or C depending on the shipping destination.
*1) The values are calculated assuming the power supplies of three-phase 400 V (50 Hz) and single-
phase 230 V (50 Hz).
*2) The worst condition includes a phase loss in the supply line.