5-10
C codes: Control Functions
Code
Name
Data setting range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer
to
page:
C01
Jump Frequency 1
0.0 to 400.0
0.1
Hz
Y
Y
0.0
–
C02
2
Y
Y
0.0
C03
3
Y
Y
0.0
C04
(Hysteresis width) 0.0 to 30.0
0.1
Hz
Y
Y
3.0
C05
Multistep Frequency 1
0.00 to 400.00 *2
0.01
Hz
Y
Y
0.00
C06
2
Y
Y
0.00
C07
3
Y
Y
0.00
C08
4
Y
Y
0.00
C09
5
Y
Y
0.00
C10
6
Y
Y
0.00
C11
7
Y
Y
0.00
C12
8
Y
Y
0.00
C13
9
Y
Y
0.00
C14
10
Y
Y
0.00
C15
11
Y
Y
0.00
C16
12
Y
Y
0.00
C17
13
Y
Y
0.00
C18
14
Y
Y
0.00
C19
15
Y
Y
0.00
C20
Jogging Frequency
0.00 to 400.00 *2
0.01
Hz
Y
Y
0.00
C21
Timer Operation
0: Disable
–
–
N
Y
0
5-60
1: Enable
C30
Frequency Command 2
0: UP/DOWN keys on keypad
–
–
N
Y
2
5-21
1: Voltage input to terminal [12] (0 to +10
VDC)
2: Current input to terminal [C1] (4 to 20 mA
DC)
3: Sum of voltage and current inputs to
terminals [12] and [C1]
4: Built-in potentiometer (POT)
7: Terminal command
UP
/
DOWN
control
C32
Analog Input Adjustment
for Terminal [12] (Gain)
0.00 to 200.00 *2
0.01
%
Y*
Y
100.0 5-36
C33
(Filter time constant) 0.00 to 5.00
0.01
s
Y
Y
0.05
5-60
C34
(Gain base point) 0.00 to 100.00 *2
0.01
%
Y*
Y
100.00 5-36
C37
Analog Input Adjustment
for Terminal [C1] (Gain)
0.00 to 200.00 *2
0.01
%
Y*
Y
100.00
C38
(Filter time constant) 0.00 to 5.00
0.01
s
Y
Y
0.05
5-60
C39
(Gain base point) 0.00 to 100.00 *2
0.01
%
Y*
Y
100.00 5-36
C40
Terminal [C1] Input
Range Selection
0: 4 to 20 mA
1: 0 to 20 mA
–
–
N
Y
0
–
C50
Bias
(Frequency command 1)
0.00 to 100.00 *2
0.01
%
Y*
Y
0.00
5-36
(Bias base point)
C51
Bias (PID command 1)
–
(Bias value) -100.00 to 100.00 *2
0.01
%
Y*
Y
0.00
C52
(Bias base point) 0.00 to 100.00 *2
0.01
%
Y*
Y
0.00
*2 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
∧
∧