INZ-TN1ZSS-E
- 7 -
AI terminal
1 AI1+
2 AI1–
Analog input 1 (AI1)
3 AI2+
4 AI2–
Analog input 2 (AI2)
5 AI3+
6 AI3–
Analog input 3 (AI3)
7 8 9 10 11 12
1 2 3 4 5 6
7 AI4+
8
AI4–
Analog input 4 (AI4)
9
AI5+
10
AI5–
Analog input 5 (AI5)
11
AI6+
12
AI6–
Analog input 6 (AI6)
AI expansion board
required
DI/DO terminal
25 26 27 28 29 30 31 32
33
34
35
36
13 14 15 16 17 18 19 20
21
22
23
24
1 2 3 4 5
6 7 8
9
10
11
12
1 DI1+
2 DI1–
Remote average value reset (option)
3 DI2+
4 DI2–
Switching input for remote instantaneous value/average value (option)
5 DI3+
6 DI3–
Remote hold (option)
7
DI4+
8
DI4–
9 DI5+
10 DI5–
Spare
11 Unassigned
12 Unassigned
13 DO1+
25 DO7+
14 DO1–
Low Light Transmission
26 DO7–
15 DO2+
27 DO8+
16 DO2–
Analyzer faulty
28 DO8–
Power OFF
17 DO3+
29 Unassigned
18 DO3–
On Hold / Under Calibration
30 Unassigned
19 DO4+
31 Unassigned
20 DO4–
Beyond the upper/lower limits
(Component 1)
32 Unassigned
21 DO5+
33 Unassigned
22 DO5–
Range identification (Component 1)
34 Unassigned
23 DO6+
35 Unassigned
24 DO6–
36 Unassigned
Note 1) Unassigned terminals may be connected to the internal circuit.
Do not use them as repeating terminals.
Note 2) Provide relay output of LD failure, LD temperature error, or connection error as analyzer faulty.
Note 3) Do not provide relay output of high gas temperature, air purge (low pressure), air purge (high
pressure), box temperature warning, PD over range or AI under.
Consult our sales representative to collectively provide relay output of alarm depending on the in-
stallation environment.