2.6.1
Devices for preventing the boiler from overheating
Thermal discharge safety device
At around 100 °C a valve opens and sends cold water to the safety
heat-exchanger to decrease the temperature.
Safety Temperature Limiter STL
Stops combustion at a max. boiler temperature of 105 °C. The pumps
continue to run.
Once the temperature has fallen below the unlocking point (approx.
95 °C), the safety temperature limiter (2) can be unlocked
mechanically.
Safety valve (provided by the customer)
Protection against over-heating/ excessive pressure:
When the boiler pressure reaches a maximum of 3 bar, the safety valve
opens and the heating water is released in the form of steam.
2.7
Safety information for installation room
•
Danger of fire due to flammable materials. No flammable materials
should be stored near the boiler.
•
Damage due to impurities in combustion air. Do not use any
solvents or cleaning agents containing chlorine in the room where
the boiler is installed.
•
Keep the air suction opening of the boiler free of dust.
•
The room where the boiler is installed must be frost-proof.