❒ Open the door
❒ Insert a sheet of paper at both the top and the bottom of the door stop between
the door and the boiler
❒ Close the door
❒ Try to pull out the sheets of paper
➥ If the paper cannot be removed:
the door is sealed.
➥ If the paper can be removed:
The door is not sealed properly - push the hinge toward the back.
⇨ See "Positioning the doors" [page 31]
On the side with the door handle
❒ Close the door
➥ The door can be closed with a normal amount of effort:
Setting OK
➥ If the door cannot be closed with the usual force or must be forced closed:
Push the locking plate toward the front
⇨ See "Positioning the doors" [page 31]
Checking the seal:
Checking the setting:
4
Assembly
Before Installation
30