4.3.3 Minimum distances in the boiler room
▪ The system should generally be set up so that it is accessible from all sides
allowing quick and easy maintenance.
▪ Regional regulations regarding necessary maintenance areas for inspecting the
chimney should be observed in addition to the specified minimum distances!
▪ Observe the applicable standards and regulations when setting up the system.
▪ Observe additional standards for noise protection
(ÖNORM H 5190 - Noise protection measures)
Dimens
ion
Description
Unit
S3 Turbo
A
Distance - front of boiler to wall
mm
800
B
Distance – side of boiler to wall
800 (200)
1)
C
Distance – back to wall
500
D
Distance – side of boiler to wall
200 (800)
1)
1.The side of the boiler where the WOS lever is located (B or D) should be at least 800 mm from the wall to allow easy access for connecting
the appliance and for maintenance work (e.g. induced draught).
4.4 Before Installation
4.4.1 Changing door stops (as needed)
The boiler comes with the door stop on the right. To change the side the door stops
are on, proceed as follows.
Changing the stop
The following example using the fuel loading door shows how to change the door stop.
The procedure is the same for changing the stop on the combustion chamber door
and pre-heating chamber door!
❒ Open the fuel loading door
4
Assembly
Setting up in the boiler room
26
Froeling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.at
All manuals and user guides at all-guides.com
all-guides.com