168
PB
TROUBLESHOOTING
Diagnostic Codes (Voltage/ Amperage)
Amperage (or Current) Diagnostic Codes
The current sensing portion of the MCS had detected that the motor is pulling more than designed amperage.
Grounded Motor
Faulty/”Demagged” Motor
Damaged MCS Board
I2T (IPM Amperage) Faults
The current sensing portion of the MCS had detected that the motor is pulling the maximum allowable amperage for an
extended period of time.
Dirty or restricted coils
Blocked or restricted Motor
Abnormally high outdoor temperature
1
2
3
1-2
1-3
2-3
Check the each terminal to the
compressor to ground.
Disconnect wires from compressor before checking. The compressor should
ohm out with the same resistance between the terminals
1.5 to 3.5 Ohms on any
two phases
5M+
Ohms
Compressor is attached to the MCS with flag terminals for easy access. If you do not get the same
resistance through each phase (+/- 0.1), then test the terminals directly.
Summary of Contents for VRP12K
Page 46: ...46 OPERATION Component Identification Indoor Coil 36k ...
Page 48: ...48 OPERATION Component Identification Outdoor Coil Monitored by 1 thermistor ...
Page 49: ...49 OPERATION Component Identification Outdoor Fan BLDC Variable Speed 600 1000 RPM ...
Page 53: ...53 OPERATION Component Identification 4 Way Reversing Valve 208 230v Reversing valve assembly ...
Page 177: ...177 UPDATING VRP FIRMWARE Or ...
Page 184: ...184 UPDATING VRP FIRMWARE Open zip file Copy to SD Card Insert into SD Card Slot ...
Page 193: ...193 UPDATING VRP FIRMWARE Retrieving VRP Data Remove SD Card from FMC and Locate DF Folder ...
Page 196: ...196 WIRINGDIAGRAMS 12 24K BTU 208 230V 7 5 10 0 KW Figure 801 Wiring Diagram ...
Page 197: ...197 WIRING DIAGRAMS 12 24K BTU 208 230V 2 5 3 4 5 0 KW Figure 802 Wiring Diagram ...
Page 198: ...198 WIRING DIAGRAMS 12 24K BTU 265V 2 5 3 4 5 0 kW Figure 803 Wiring Diagram ...
Page 199: ...199 WIRING DIAGRAMS 12 24K BTU 265V 7 5 10 kW Figure 804 Wiring Diagram ...
Page 200: ...200 WIRING DIAGRAMS 36K BTU 208 230V Figure 805 Wiring Diagram ...