89
PB
22
Final Drain Installation
Unit Drain Installation
NOTE:
Failure to follow the following procedures may result in serious property damage. A field supplied secondary
condensate pan may be required. Check with local codes. In case of drainage system blockage, the unit base will allow
excess water to flow out of the unit through the plenum and the architectural louver. It is critical to ensure that the drain
-
age path is not blocked or obstructed in any way during installation.
1)
Connect the supplied drain kit must be connected to one of the three (left, right or rear) 3/4” FPT connections on
the unit basepan. Use of rear fitting without connection to DWV system (drain, waste, vent) may result in staining
of the outside wall.
2)
Insert the provided 3/4” nipple into the determined connection using field-supplied Teflon tape or pipe joint
compound.
3)
With the slip end of a 3/4” union, connect to the nipple with Teflon tape or pipe joint compound.
4)
Hand-tighten all fittings to prevent damage to unit or fittings.
5)
Install a field-supplied drain system to the slip end of the union. A trap is recommended and drain connections
should be connected to building DWV system. Pitch the drain line of a 1/4” downward slope for every foot (1’) of
lateral horizontal run to the DWV.
6)
Plug the two unused connection ports with the two provide 3/4” pipe plugs and field-supplied Teflon tape or
pipe joint compound. High tighten to prevent damage to the unit or fittings. Do not thread metal or copper pipe
fittings directly into unit.
7)
Check the system for leaks.
”
”
”
INSTALLATION
Unit Drain Installation
Summary of Contents for VRP12K
Page 46: ...46 OPERATION Component Identification Indoor Coil 36k ...
Page 48: ...48 OPERATION Component Identification Outdoor Coil Monitored by 1 thermistor ...
Page 49: ...49 OPERATION Component Identification Outdoor Fan BLDC Variable Speed 600 1000 RPM ...
Page 53: ...53 OPERATION Component Identification 4 Way Reversing Valve 208 230v Reversing valve assembly ...
Page 177: ...177 UPDATING VRP FIRMWARE Or ...
Page 184: ...184 UPDATING VRP FIRMWARE Open zip file Copy to SD Card Insert into SD Card Slot ...
Page 193: ...193 UPDATING VRP FIRMWARE Retrieving VRP Data Remove SD Card from FMC and Locate DF Folder ...
Page 196: ...196 WIRINGDIAGRAMS 12 24K BTU 208 230V 7 5 10 0 KW Figure 801 Wiring Diagram ...
Page 197: ...197 WIRING DIAGRAMS 12 24K BTU 208 230V 2 5 3 4 5 0 KW Figure 802 Wiring Diagram ...
Page 198: ...198 WIRING DIAGRAMS 12 24K BTU 265V 2 5 3 4 5 0 kW Figure 803 Wiring Diagram ...
Page 199: ...199 WIRING DIAGRAMS 12 24K BTU 265V 7 5 10 kW Figure 804 Wiring Diagram ...
Page 200: ...200 WIRING DIAGRAMS 36K BTU 208 230V Figure 805 Wiring Diagram ...