UPDATING VRP FIRMWARE
VRP Remote Upgrade Procedure
There are two stages that will be displayed for the majority of the time. The first is while the WC
is transferring files to the FMC, it will display a “6” and the Communication Icon will blink. This stage
will last approximately 7-8 minutes.
When the FMC is sending a file to the MCS, the digits “5L” will be displayed. This stage will last
approximately 11-12 minutes:
This will persist until near the end of the Remote Upgrade process as the WC is waiting to hear
if the MCS and/or FMC upgrade process was successful. After this stage a “9” will be displayed for
approximately 1-2 minutes:
After the remote upgrade has been completed, the WC screen may restart or go blank. Remove
the SD Card to restart the WC:
3
Summary of Contents for VRP12K
Page 46: ...46 OPERATION Component Identification Indoor Coil 36k ...
Page 48: ...48 OPERATION Component Identification Outdoor Coil Monitored by 1 thermistor ...
Page 49: ...49 OPERATION Component Identification Outdoor Fan BLDC Variable Speed 600 1000 RPM ...
Page 53: ...53 OPERATION Component Identification 4 Way Reversing Valve 208 230v Reversing valve assembly ...
Page 177: ...177 UPDATING VRP FIRMWARE Or ...
Page 184: ...184 UPDATING VRP FIRMWARE Open zip file Copy to SD Card Insert into SD Card Slot ...
Page 193: ...193 UPDATING VRP FIRMWARE Retrieving VRP Data Remove SD Card from FMC and Locate DF Folder ...
Page 196: ...196 WIRINGDIAGRAMS 12 24K BTU 208 230V 7 5 10 0 KW Figure 801 Wiring Diagram ...
Page 197: ...197 WIRING DIAGRAMS 12 24K BTU 208 230V 2 5 3 4 5 0 KW Figure 802 Wiring Diagram ...
Page 198: ...198 WIRING DIAGRAMS 12 24K BTU 265V 2 5 3 4 5 0 kW Figure 803 Wiring Diagram ...
Page 199: ...199 WIRING DIAGRAMS 12 24K BTU 265V 7 5 10 kW Figure 804 Wiring Diagram ...
Page 200: ...200 WIRING DIAGRAMS 36K BTU 208 230V Figure 805 Wiring Diagram ...