S90-010 CS (APR 08) FRICK
®
QUANTUM™ COMPRESSOR CONTROL PANEL
Page 66 COMMUNICATIONS SETUP
SETTINGS – CONTINUED
Frick
®
Address
AB
Address
Modbus
Address
Read
Only
Description of Data
1231
N23:176
41232
PID 2 High Limit
1232
N23:177
41233
PID 2 Low Limit
1233 N23:178 41234
PID 2 Off Value
1234
N23:179
41235
X
PID 5 Control
1235
N23:180
41236
X
PID 5 Action - Forward/Reverse Acting
1236
N23:181
41237
PID 5 Setpoint
1237
N23:182
41238
PID 5 DeadBand
1238
N23:183
41239
PID 5 Proportional Gain
1239
N23:184
41240
PID 5 Integral Gain
1240
N23:185
41241
PID 5 Derivative Gain
1241
N23:186
41242
PID 5 High Limit
1242
N23:187
41243
PID 5 Low Limit
1243 N23:188 41244
PID 5 Off Value
1244
N23:189
41245
X
PID 6 Control
1245
N23:190
41246
X
PID 6 Action - Forward/Reverse Acting
1246
N23:191
41247
PID 6 Setpoint
1247
N23:192
41248
PID 6 DeadBand
1248
N23:193
41249
PID 6 Proportional Gain
1249
N23:194
41250
PID 6 Integral Gain
1250
N23:195
41251
PID 6 Derivative Gain
1251
N23:196
41252
PID 6 High Limit
1252
N23:197
41253
PID 6 Low Limit
1253 N23:198 41254
PID 6 Off Value
1254
N23:199
41255
X
PID 1 while Running selection but off Operation
1255
N23:200
41256
X
PID 2 while Running selection but off Operation
1256
N23:201
41257
X
PID 5 while Running selection but off Operation
1257
N23:202
41258
X
PID 6 while Running selection but off Operation
1258
N23:202
41259
Economizer Override value
1259 N23:203 41260
Liquid Slug Alarm
1260 N23:204 41261
Liquid Slug Shutdown
1261
N23:205
41262
Maintenance for Oil Analysis
1262
N23:206
41263
Maintenance for Change Filters
1263
N23:207
41264
Maintenance for Clean Oil Strainers
1264
N23:208
41265
Maintenance for Clean Liquid Strainers
1265
N23:209
41266
Maintenance for Change Coalescers
1266
N23:210
41267
Maintenance for Check and Clean Suction Screen
1267
N23:211
41268
Maintenance for Vibration Analysis
1268
N23:212
41269
Maintenance for Check Coupling/Alignment
1269
N23:213
41270
Maintenance for Grease Motor
1270
N23:214
41271
Maintenance for User Maintenance Setpoint 1
1271
N23:215
41272
Maintenance for User Maintenance Setpoint 2
1272
N23:216
41273
Maintenance for User Maintenance Setpoint 3
1273
N23:217
41274
Maintenance for User Maintenance Setpoint 4
1274
N23:218
41275
Maintenance for User Maintenance Setpoint 5
1275
N23:219
41276
Maintenance for User Maintenance Setpoint 6
1276
N23:220
41277
Interval for Oil Analysis
1277
N23:221
41278
Interval for Change Filters
1278
N23:222
41279
Interval for Clean Oil Strainers
1279
N23:223
41280
Interval for Clean Liquid Strainers
1280
N23:224
41281
Interval for Change Coalescers
1281
N23:225
41282
Interval for Check and Clean Suction Screen
1282
N23:226
41283
Interval for Check Vibration Analysis
1283
N23:227
41284
Interval for Check Coupling/ Alignment
1284
N23:228
41285
Interval for Grease Motor
1285
N23:229
41286
Interval for User Maintenance Setpoint 1
1286
N23:230
41287
Interval for User Maintenance Setpoint 2
1287
N23:231
41288
Interval for User Maintenance Setpoint 3
1288
N23:232
41289
Interval for User Maintenance Setpoint 4
1289
N23:233
41290
Interval for User Maintenance Setpoint 5
1290
N23:234
41291
Interval for User Maintenance Setpoint 6
1291
N23:235
41292
X
Slide Valve Unload Assist Enable/Disable
1292
N23:236
41293
User Selectable Control Channel #