S90-010 CS (APR 08) FRICK
®
QUANTUM™ COMPRESSOR CONTROL PANEL
Page 14 COMMUNICATIONS SETUP
CHANGE COMPRESSOR MODE COMMAND:
#IDMCmID Change mode to m.
M or O = off A = Autocycle R = remote
Return message -
A
followed by the
ID
,
CR
,
LF
if
successful.
CHANGE SLIDE VALVE MODE COMMAND:
#IDMVmID Change Slide Valve mode.
to m. A = auto R = remote
Return message -
A
followed by the
ID
,
CR
,
LF
if
successful.
CLEAR FAILURE COMMAND:
#IDKFID Clear Fails
Return message -
A
followed by the
ID
,
CR
,
LF
if
successful.
CLEAR ANTIRECYCLE COMMAND:
#IDKRID Clear Recycle Delay
Return message -
A
followed by the
ID
,
CR
,
LF
if
successful.
RETURN FAILURE COMMAND:
#IDF Return Discrete Failure List Command:
Returns a 24 char data string followed by ID, CR, LF.
Position Alarm
Description
1
High Discharge Pressure Shutdown
2
High Discharge Pressure Alarm
3
Low Suction Pressure Shutdown
4
Low Suction Pressure Alarm
5
Low Oil Pressure Shutdown and/or
Differential Oil Pressure Shutdown
6
Low Oil Pressure Alarm
7
High Oil Temperature Shutdown
8
High Oil Temperature Alarm
9
Low Oil Temperature Shutdown
10
Low Oil Temperature Alarm
11
High Discharge Temperature Shutdown
12
High Discharge Temperature Alarm
13
Compressor Aux. Fail- Shutdown
14
Pump Aux. Fail- Shutdown
15
Oil Level Shutdown
16 Unused
-
0
17
High Oil Filter Pressure Alarm
18 Unused
-
0
19
Auxiliary 1 Alarm/Shutdown
20
Auxiliary 2 Alarm/Shutdown
21
Low Motor Current - Shutdown
22 Sensor
Fault
23 Unused
-
0
24 Unused
-
0
0 = safe 1 = alarm/shutdown