S90-010 CS (APR 08) FRICK
®
QUANTUM™ COMPRESSOR CONTROL PANEL
Page 54 COMMUNICATIONS SETUP
STARTER PANEL I/O (READ ONLY): Continued
Frick
®
Address
AB
Address
Modbus
Address
Description of Data
Value Codes
209 N10:113
40210
Starter
Wiring
210
N10:114
40211
Starter Size
0 = A1
1 = A2
2 = B1
3 = B2
4 = B3
5 = B4
6 = C1
7 = C2
8 = C3
9 = D1
10 = D2
11 = D3
12 = E1
13 = E2
211 N10:115
40212
DBS
Version
212 N10:116
40213
Bypass
Time
213
N10:117
40214
Elapsed Run Time Min
207
N10:111
40208
Thermal Overload Status
EXTRA PORT (READ ONLY):
Frick
®
Address
AB
Address
Modbus
Address
Description of Data
223 N10:127 40224
Board
Temperature
ANALOG OUTPUTS BOARD #1 (READ ONLY):
Frick
®
Address
AB
Address
Modbus
Address
Description of Data
223 N10:127 40224
Board
Temperature
241 N10:145
40242
PID/Programmable
242 N10:146
40243
PID/Programmable
243
N10:147
40244
Slide Valve Position
244 N10:148
40245
Remote
Control
ANALOG OUTPUTS BOARD #2 (READ ONLY):
Frick
®
Address
AB
Address
Modbus
Address
Description of Data
245
N10:149
40246
PID/Programmable
246
N10:150
40247
PID/Programmable
247
N10:151
40248
Variable Speed Drive
248
N10:152
40249
Condenser Analog Output