S90-010 CS (APR 08) FRICK
®
QUANTUM™ COMPRESSOR CONTROL PANEL
Page 26 COMMUNICATIONS SETUP
Read Message Setup Example
Instruction Entry for Message Block MG14:0:
Communication Command: SLC Typed Logical Read
PLC-5 Data Table Address: N9:3
Size in Elements: 20
Local/Remote: Local
Local Node Address: 004 (Quantum™ Panel’s ID)
Destination Data Table Address: N10:1
Port Number: 0
(Refer to the
Allen-Bradley Programming Overview
Section for more information)
Allen-Bradley Programming Overview
This section contains programming examples for reading
data from, and writing data to the Frick
®
Quantum™
control panel from an Allen Bradley (AB) SLC500 or PLC5
processor. AB RSLogix500 programming software has
been used for the following examples, however, these
examples can also be used for the AB RSLogix5 software.
Channel Configuration
The following are representations of the channel
configuration screens from the AB RSLogix500
programming software for the SLC500. Enter values as
shown in order to establish communications via AB
Protocol.
General Configuration
System Configuration