FRICK
®
QUANTUM™ COMPRESSOR CONTROL PANEL S90-010 CS (APR 08)
COMMUNICATIONS SETUP Page 49
DIGITAL BOARD 1 (READ ONLY):
Frick
®
Address
AB
Address
Modbus
Address
Description of Data
Module
Type
Value Codes
0 N50:0
40001
Compressor
Start
Output
0 = Off
1 = On
1 N50:1
40002
Compressor
Auxiliary
Input
0 = Off
1 = On
2
N50:2
40003
Oil Pump #1 Start/Run
Output
0 = Off
1 = On
3
N50:3
40004
Oil Pump #1 Auxiliary
Input
0 = Off
1 = On
4
N50:4
40005
Slide Valve Load
Output
0 = Off
1 = On
2 = Off
5
N50:5
40006
Slide Valve Unload
Output
0 = Off
1 = On
2 = Off
6
N50:6
40007
Slide Stop Increase
Output
0 = Off
1 = On
2 = Off
7
N50:7
40008
Slide Stop Decrease
Output
0 = Off
1 = On
2 = Off
8 N50:8
40009
Liquid
Injection
Output
0 = Off
1 = On
9
N50:9
40010
Hi-Vi Liquid Injection
Output
0 = Off
1 = On
10 N50:10
40011
Economizer
Output
0 = Off
1 = On
11 N50:11
40012
Balance
Piston
Output
0 = Off
1 = On
12 N50:12
40013
Oil
Level
Input
0 = Off
1 = On
13
N50:13
40014
High Liquid Level from System
Input
0 = Off
1 = On
14 N50:14
40015
Enclosure
Heater
Output
0 = Off
1 = On
15
N50:15
40016
Hot Gas Bypass
Output
0 = Off
1 = On
16 N50:16
40017
Aux.
#1
Input
0 = Off
1 = On
17 N50:17
40018
Aux.
#2
Input
0 = Off
1 = On
18
N50:18
40019
Process Mode Select
Input
0 = 1
st
Mode
1 = 2
nd
Mode
19 N50:19
40020
Capacity
Control Setpoint #2
Input
0 = Mode 1
1 = Mode 2
20 N50:20
40021
Oil
Heater
Output
0 = Off
1 = On
21 N50:21
40022
Alarm
Output
0 = None
1 = Alarm
22 N50:22
40023
Shutdown
Output
0 = Shutdown
1 = None
23 N50:23
40024
Power
Assist
Output
0 = Off
1 = On