S90-010 CS (APR 08) FRICK
®
QUANTUM™ COMPRESSOR CONTROL PANEL
Page 28 COMMUNICATIONS SETUP
Message Read Setup Screen
The following setup screen is programmed to obtain 28
consecutive data files from the Quantum™ (ID#1) N10:1
register and place them into the SLC500’s N10:1 through
N10:28 register.
•
This Controller: SLC500
•
Data Table Address: Data file location in the
SLC500
•
Size in Elements: # of data file to read
•
Channel: Port location on the SLC processor
(Channel 0 is the RS-232 port)
•
Target Device: Quantum™ Panel
•
Data Table Address: Data file location in the
Quantum™ controller.
•
Local Node: Quantum™ ID# (Octal)