Page 62
Rev 3 Service Manual MCC Hot / Cold 2021
9.4
Parameter MCC Hot Settings (Self Serve)
Doc. nr.
9124410
Rev.
Registration form.
Danfoss ERC 211 – 65 °C
Pagina 1 van 1
MCC Hot SS
Note:
Use tool
STICK 18
for inserting parameters and only change yellow arced parameters manually!
r00
Temperature set point
65
°C
r01
Differential
1
K
r02
Min set point limitation
40
°C
r03
Max set point limitation
70
°C
r04
Display offset
0
°C
r05
Display unit (°C/°F)
°C
r09
Calibration of Sair
0
°C
r12
Main switch
1
r13
Night set back
0
r40
Thermostat reference displacement
0
r96
Pull-down duration
0
r97
Pull-down limit temperature
0
A03 Delay for temperature alarm
(normal conditions)
30
min
A12 Delay for temperature alarm
(pull down/start-up/defrost)
60
min
A13 High temperature alarm limit
100
°C
A14 Low temperature alarm limit
-30
°C
A27 DI1 delay
30
min
A37 Condenser high alarm limit
80
°C
A54 Condenser high block limit
85
°C
A72 Voltage protection enable
no
A73 Minimum cut-in voltage
0
V
A74 Minimum cut-out voltage
0
V
A75 Maximum voltage
270
V
d01
Defrost method
(no=no defrost, nAt=natural)
no
d02
Defrost stop temperature
6
°C
d03
Defrost Interval
8
hr.
d04
Max. defrost time
30
min
d05
Defrost delay at power up
0
min
d06
Drip delay
0
min
d10
Defrost stop sensor
(non=time, Air=Sair)
non
d18
Compressor accumulated
0
hr.
d30
Defrost delay after pull-down
0
min
c01
Compressor minimum ON time
0
min
c02
Compressor minimum OFF-time
0
min
c04
Compressor OFF delay
0
sec
c70
Zero crossing selection
yES
o01
Delay of outputs
0
sec
o02
DI1 configuration
oFF
o03
Serial address
0
o05
Password
no
o06
Sensor type selection
(n5=NTC5 K, n10=NTC10 K, Ptc=PTC,
Pt1=Pt1000)
Ptc
o07
Cooling/heating
(rE=refrigeration / Ht=heat)
Ht
o15
Display resolution (°C)
0.1
o23
Relay counter
0
o61
Predefined applications
AP0
o67
Save settings as factory
no
o91
Display at defrost
d
P73 DI1 input polarity
no
P76 Keyboard lock enable
no
u01
Air temperature (Sair)
-
°C
u02
Read the present regulation refer-
ence
-
u10
DI1 input
-
u13
Status of night operation
-
u58
Compressor relay status
-
-
u80
Firmware version readout
-
Summary of Contents for Cold MCC
Page 20: ...Page 20 Rev 3 Service Manual MCC Hot Cold 2021 Circuit diagram evaporator tray...
Page 21: ...Rev 3 Service Manual MCC Hot Cold 2021 Page 21 Wiring diagram evaporator tray...
Page 29: ...Rev 3 Service Manual MCC Hot Cold 2021 Page 29 5 1 MCC 90 Drop in Dimensions Self Serve...
Page 39: ...Rev 3 Service Manual MCC Hot Cold 2021 Page 39 6 0 Installation Front door section...
Page 77: ...Rev 3 Service Manual MCC Hot Cold 2021 Page 77 Page intentionally left blank...
Page 103: ...Rev 3 Service Manual MCC Hot Cold 2021 Page 103 Page intentionally left blank...
Page 139: ...Rev 3 Service Manual MCC Hot Cold 2021 Page 139 17 0 Electrical schematics MCC Cold Self Serve...
Page 140: ...Page 140 Rev 3 Service Manual MCC Hot Cold 2021...
Page 141: ...Rev 3 Service Manual MCC Hot Cold 2021 Page 141 17 1 Electrical wiring MCC Cold Self Serve N L...
Page 142: ...Page 142 Rev 3 Service Manual MCC Hot Cold 2021...
Page 143: ...Rev 3 Service Manual MCC Hot Cold 2021 Page 143 17 2 Circuit Diagram MCC Hot Full Serve...
Page 144: ...Page 144 Rev 3 Service Manual MCC Hot Cold 2021 17 3 Electrical wiring MCC Hot Full Serve...
Page 145: ...Rev 3 Service Manual MCC Hot Cold 2021 Page 145...
Page 146: ...Page 146 Rev 3 Service Manual MCC Hot Cold 2021...