74
DEF installation
FMP-TEM wiring
The FMP-TEM Temperature Sensor includes 2 electrical connectors for installation inside the
junction box only.
1.
Use the 2 moisture-resistant connectors provided for each sensor. For these splices, the
wire insulation is NOT cut-back (NOT Stripped)
2.
Insert the 2 brown wires into two separate opening of the first connector. Make sure the
wires are fully inserted and seated at the end of the connector.
3.
Insert the 2 black wires into two separate opening of the first connector. Make sure the
wires are fully inserted and seated at the end of the connector.
4. Squeeze each connector together using 8” slip-joint pliers (position the pliers jaws on the
connector perpendicular to the wires and drive the black cap down almost flush to the edge of
the connector body)
.
After Crimp
To
Console
To
FMP-TEM
Before Crimp
End view of splice
White wire of Sensor (-)
Brown wire of
field cable (+)
Black wire of
field cable (-)
Black wire
of Sensor (+)