68
Alarms
When a T5 ATG is in alarm, the Alarm LED on the front of the ATG will flash. If the line has
been programmed to shut down the pump on failed test (in the FMS Setup), the pump will be
unavailable for all system tests and dispensing until the line with the active alarm is manually
reset. If the condition still exists after reset, the alarm will return. A service visit may be required
to identify and correct the condition.
WARNING
: Turn off power to the ATG before you install or remove a module or perform any
maintenance procedure while the ATG door is open.
IMPORTANT
: Read the "Operating precautions" in the "Introduction" chapter before you perform
any maintenance on the ATG.
NOTE:
If this guide is not able to help you correct a warning or alarm, please contact FFS
Technical Support at 1.800.984.6266.
LS-500 alarms and warnings
Alarms during the learn process
Alarm
Symptom
Possible Cause
Resolution
Failed to
pressure up
STP is not turning
on.
Verify that the 4-20
transducer is a relay / TPI
input.
Check the programming
Is the pump controller
powered on?
Check the controller
If controlled by a relay, is
the common of the relay
wired to 110 Volts?
Test the voltage on the
relay common
Is another STP turning on?
Check the other STPs
STP is turning on,
but the LS500
doesn’t see the
pressure change
Is the 4-20 transducer in
alarm?
Check alarms
Is the wrong transducer
mapped?
Check programming
Is the clamp valve down?
Look at the pressure gauge
on the needle valve kit for
operating pressure
Line is not
configured
Programming mapping
error
Verify programming
Program error
detected
ATG software error
Reboot the ATG