Relay Module (RM)
The RLY is a non-intrinsically safe module that has 8 identical Form C output channels. Each
channel has a fuse and three terminals. Each channel can be configured as NO or NC with the
power off by wiring to the appropriate terminals. A T5 Series ATG can accommodate up to 24
outputs (8 outputs on up to 3 modules) as space allows. The diagrams below illustrate two
examples of positive shutdown upon alarm conditions.
Relay Module
RUN
ERR
NO8
C8
NC8
NO7
C7
NC7
NO6
C6
NC6
NO5
C5
NC5
NO4
C4
NC4
NO3
C3
NC3
NO2
C2
NC2
NO1
C1
NC1
or
STP-CBS
Relay Module disables the
hook signal to the pump
upon alarm conditions.
110/240 VAC
Electrical Panel
Line
Neutral
Switching Current 2A Max.
Switching Power 1500 VA Max.
NOTE:
The STP-CBS controller controls the DEF Pump Motor Assembly.
Relay Module Specifications
Number of Channels:
8 Form C
Contact Rating:
2A @ 250 VAC
2A @ 30 VDC