39
Fuel management system
Group Name
Parameter Name
Parameter Value
Fuel Management System
Ullage Percent
95%
Delivery Delay
5 min
Correction Temperature
60.00 °F
High Product Limit
Level
Static Tank Testing
Region
United States
Monthly Leak Test
Threshold
0.20 gph
Yearly Leak Test Threshold
0.10 gph
Sentinel Mode Threshold
3.00 gph
Confidence
99%
Minimum Leak Test Time
2 hr
Maximum Leak Test Time
8 hr
Alarm On Precision Leak
Test Failure
No
Tanks
Number of Tanks
7
Tank 1
Name
Unleaded
Type
Special 1
Manifolded
No
Product #
1
Delivery Threshold
200.0 gal
Theft Threshold
5.0 gal
Monthly Compliance
No
Annual Compliance
No
Probe
Module
FMS Probe Module
Channel
Unlead Probe
Type
Standard 113
Ratio
1 to 1 tip to head
Float Type
Ethanol Blends/Phase Separation
Water Float
Yes
Gradient
Calibration number from probe label
Product Offset
0.00 in
Water Offset
0.0 in
Generator Mode
Enable
No
SCALD
Enable
No
Qualify
14%
Limits
High High Product Level
Limit
97.00 in
High Product Level Limit
90.00 in
High Water Level Limit
2.00 in
Low Product Volume Limit
3,000.0 gal
Low Low Product Volume
Limit
1,500.0 gal