15
Mode of operation
Indicates that the unit is connected to an AC source
Indicates that the unit is connected to a PV panel
Indicates that the inverter is operating in bypass mode
Indicates that the AC source is charging the battery
Indicates that the DC-AC conversion is enabled
Mute control
Indicates that the audible alarm is disabled
Item
Description
Selectable parameters
00
Exit the setting screen
mode
Escape
01
Output source priority
setting:
If multiple power sources
are available, this controls
which source is used first
to power the loads
USB: Utility first (default)
Utility will provide power to the loads
as first priority
Solar and battery energy will provide
power to the loads only when the AC
source is not available
SOL: Solar first
Solar energy provides power to the
loads as first priority
If solar energy is not enough to power
all the connected loads, the AC
source will assist PV
Batteries will be used if neither PV nor
AC is available or insufficient
SBU priority
Solar energy provides power to the
loads as first priority
If solar energy is not enough to power
all the connected loads, battery
power will assist PV
AC source is only used if the battery
drops to the low battery warning level
or when it reaches the AC transfer
voltage setting in item 12
6. Advanced operation
6.1. Main LCD configuration screen
To enable the configuration screen mode, press and hold the
ENTER
button for 3 seconds. Use the
UP
or
DOWN
buttons to go through the available parameters within each menu item. Pressing the
ENTER
button again allows the
selected item to be set. To exit, simply press the
ESC
button.
Summary of Contents for FIO-P11K12
Page 1: ...1KW User Manual 2 y ear w arran ty Off grid hybrid solar inverter and charger FIO P11K12...
Page 34: ...NOTES...
Page 35: ...NOTES...
Page 36: ......