19
23
Bypass function:
When enabled, the unit will
transfer to line mode if an
overload occurs in battery
mode.
Bypass disable (default)
Bypass enable
25
Record fault code
Record enable
Record disable (default)
26
Bulk charging voltage
(Constant voltage CV)
Default setting: 14.1V
This is selectable when item 05 is set to USER-DEFINED
- Selection range: 12.0V to 14.6V
Increments of 0.1V per click
27
Float charging voltage
Default setting: 13.5V
This is selectable when item 05 is set to USER-DEFINED
- Selection range: 12.0V to 14.6V
Increments of 0.1V per click
29
Low DC cutoff voltage
Default setting: 10.5V
It is the low battery voltage setting which shuts down the inverter. This
is selectable when item 05 is set to USER-DEFINED
- Selection range: 10.0V to 12.0V
Increments of 0.1V per click
The setting value remains fixed regardless of the percentage of
connected loads