background image

Notes:

- Reduce the maximum length by 1
metre for each 90° bend.
- Reduce the maximum length by 0,5
metres for each 45° bend.
- Models 

RTFS 18

and 

RTFS 24

: for

installations with an equivalent length
of less than 2+2 metres, install a 42
mm diaphragm on the air intake.
- Models 

RTFS 32

and 

RTFS 36

: for

installations with an equivalent length
of less than 9+9 metres, install a 40
mm diaphragm on the air intake.

Type C32

This boiler is designed to be connec-
ted up to vertical flue and intake termi-
nals, connected to the outside air by
means of a coaxial pipe or double
pipes.
The distance between the air intake
pipe and the smoke flue pipe must be
at least 250 mm and both terminals
are to be positioned within a square
with 500 mm sides.

Air intake/smoke flue coaxial pipe,

diameter 60/100 mm.

Configuration allowed:
N° 1 flanged stub pipe
N° 4 metres coaxial pipe
N° 1 roofed intake/flue terminal.

Notes:

- Reduce the maximum length by 1
metre for each 90° bend.
- Reduce the maximum length by 0,5
metres for each 45° bend.

• Air intake / smoke flue double 80
mm diameter piping

Configuration allowed:
N° 2 flanged stub pipes
N° 19 metres of air intake piping
N° 19 metres of smoke flue piping
N° 1 air intake terminal
N° 1 smoke flue terminal

Notes:

- Reduce the maximum length by 1
metre for each 90° bend.
- Reduce the maximum length by 0,5
metres for each 45° bend.

- Models 

RTFS 18 

and 

RTFS 24

: for

installations with an equivalent length
of less than 2+2 metres, install a 42
mm diaphragm on the air intake.
- Models 

RTFS 32

and 

RTFS 36

: for

installations with an equivalent length
of less than 9+9 metres, install a 40
mm diaphragm on the air intake.

Type C42

This boiler is designed to be connec-
ted up to a collective smoke flue
system made up of two pipes, one for
the combustion-supporting air intake
and the other for the removing the
smoke produced by combustion, by
means of a coaxial pipe or double
pipes.
The distance between the air intake
pipe and the smoke flue pipe must be
at least 250 mm and both terminals
are to be positioned within a square
with 500 mm sides.

The smoke flue is to comply with cur-
rent standards.

• Air intake/smoke flue double 80
mm diameter piping

Configuration allowed:
N° 2 flanged stub pipes
N° 2 metres of air intake piping
N° 2 metres of smoke flue piping

Notes:

- Reduce the maximum length by 1
metre for each 90° bend.
- Reduce the maximum length by 0,5
metres for each 45° bend.
- Models RTFS 18 and RTFS 24:
install a 42 mm diaphragm on the air
intake.
-  Model RTFS 32 and RTFS 36: install
a 40 mm diaphragm on the air intake.

Type C52

This boiler is designed to be connec-
ted up to separate flue and combu-
stion-supporting air intake pipes.

These pipes may open out into
areas at differing pressures.

The two terminals may not be posi-
tioned on opposite sides.

• Air intake/smoke flue double 80
mm diameter piping
Roof-mounted flue pipe
Configuration allowed:

N° 2 flanged stub pipes
N° 1 metre of air intake piping
N° 30 metres of smoke flue piping
N° 1 air intake terminal
N° 1 roof-mounted smoke flue terminal

Notes:
- 1 metre of air intake piping is
equivalent to 2 metres of vertical
smoke flue piping.

-  Reduce the maximum length by 1
metre for each 90° bend.
- Reduce the maximum length by
0,5 metres for each 45° bend.
- Models 

RTFS 18

and 

RTFS 24:

for

installations with an equivalent verti-
cal flue pipe length of less than 18
metres, install a 40 mm diaphragm
on the air intake.
- Model 

RTFS 32

and 

RTFS 36

: for

installations with an equivalent verti-
cal flue pipe length of less than 4
metres, install a 42 mm diaphragm
on the air intake.

Wall-mounted flue pipe
Configuration allowed:

N° 2 flanged stub pipes
N° 19 metres of air intake piping
N° 19 metres of smoke flue piping
N° 1 air intake terminal
N° 1 smoke flue terminal

Notes:
-  1,6 metres of air intake piping is
equivalent to 1 metres of horizon-
tal smoke flue piping.

-  Reduce the maximum length by 1
metre for each 90° bend.
- Reduce the maximum length by
0,5 metres for each 45° bend.
- Models 

RTFS 18

and 

RTFS 24

: for

installations with an equivalent
length of less than 9+9 metres,
install a 40 mm diaphragm on the air
intake.

10

Summary of Contents for BALI RTFS E 18

Page 1: ...BALI RTFS IST 03 C 080 01 INSTALLATION OPERATION AND MAINTENANCE CE 49BN3788 GB...

Page 2: ...1 Dear Customer Thank you for choosing and buying one of our boilers Please read these instructions carefully in order to install operate and maintain this equipment properly...

Page 3: ...o specific separated collection areas Keep the packing out of reach of chil dren as by its very nature it may constitute a source of danger Should the equipment break down and or function defectively...

Page 4: ...3 2 1 Packing pag 9 3 2 2 Choosing the installation position for the boiler pag 9 3 2 3 Installing the Boiler pag 9 3 2 4 Ventilation of Boiler Rooms pag 9 3 2 5 Smoke stack system pag 9 3 2 6 On site...

Page 5: ...tioning It must be reset manually Burner cut out LED Red 6 This light indicates that the burner safety device has tripped due to a malfunction Burner operation LED Yellow 7 This light indicates that t...

Page 6: ...fety thermo stat cut out has tripped and must be reset manually This is due to an operating fault and an authorised Service Centre or qualified person nel must be contacted for mainte nance 1 2 4 Cut...

Page 7: ...ed for in the current stan dards for this type of product The main technical characteristics of the BALI boiler are listed below High performance cast iron heat exchanger Insulation in glass wool with...

Page 8: ...GAS G 1 2 G 1 2 G 1 2 G 1 2 RETURN G 1 G 1 G 1 G 1 FEED G 1 G 1 G 1 G 1 Model RTFS E 18 RTFS E 24 RTFS E 32 RTFS E 36 L 510 510 610 610 2 2 Dimensions 7 fig 2...

Page 9: ...V Hz W A C Kg h N mm mm mbar Stm3 h mm C Kg h N mm mm mbar kg h EC Performance Class EC PIN Category Type Thermal Power Thermal Capacity Performance at nominal load Performance at reduced load 30 Main...

Page 10: ...ler to the system s feed and return pipes Remember that the plumbing system must include all the safety and control elements required in terms of current standards safety valve water pressure switch h...

Page 11: ...smoke flue pipe must be at least 250 mm and both terminals are to be positioned within a square with 500 mm sides The smoke flue is to comply with cur rent standards Air intake smoke flue double 80 mm...

Page 12: ...mp to prevent it being torn out This boiler must be connected to a 230V 50Hz electrical power supply When forming the connection respect the phase neutral polarity Installation standards must be com p...

Page 13: ...with a drain stopcock at the front of the unit that can be used to empty the system 3 4 Starting the Boiler 3 4 1 Preliminary Checks Before starting the boiler it is best to check that The smoke flue...

Page 14: ...R on the printed circuit VG Gas valve TM Contact Timer optional mar ked TIMER on the printed cir cuit PZ Ignition spark unit PA Water pressure switch optio nal marked with the pressure switch symbol o...

Page 15: ...that indicates the type of gas and pres sure for which the equipment is set 4 MAINTENANCE In order to ensure that the equip ment is efficient and that it functions correctly maintenance must be car ri...

Page 16: ...ocenigo 123 Tel 0365 878 31 Fax 0365 878361 e mail fondital fondital it export01 fondital it www fondital it Fondital reserves the right to make any changes it deems necessary without notice Fondital...

Reviews: