Certifying Twisted Pair Cabling
Monitoring Impulse Noise
3-35
3
The test takes noise voltage samples every second on pair
3, 6. The test produces a PASS/FAIL result if the selected
standard specifies a noise limit.
Note
Monitoring impulse noise without a smart remote
may produce unreliable test results.
To monitor impulse noise:
1
Attach twisted pair link interface adapters to the tester
and smart remote.
2
Turn the rotary switch to MONITOR and turn on the
smart remote; then connect to the testers to the ends
of the cabling.
3
Press
P
.
4
To adjust the noise threshold, press
L
Stop; then use
A D
to change the value. Press
P
to
resume testing.
Tip: Fluke Networks recommends a noise threshold of
30 mV with an average pulse rate below 0.01/sec for
testing 1000BASE-T (Gigabit Ethernet) cabling.
To stop the test at any time, press
I
.
Note
If you disconnect the tester and smart remote
during the impulse noise test, it takes several
minutes for the remote to stop testing.
Figure 3-25 describes the impulse noise test results.
Summary of Contents for DTX-1800
Page 4: ......
Page 18: ...DTX Series CableAnalyzer Technical Reference Handbook xiv ...
Page 132: ...DTX Series CableAnalyzer Technical Reference Handbook 4 8 ...
Page 158: ...DTX Series CableAnalyzer Technical Reference Handbook 6 14 ...
Page 270: ...DTX Series CableAnalyzer Technical Reference Handbook 8 62 ...
Page 284: ...DTX Series CableAnalyzer Technical Reference Handbook 10 10 ...
Page 304: ...DTX Series CableAnalyzer Technical Reference Handbook 11 20 ...
Page 372: ...DTX Series CableAnalyzer Technical Reference Handbook A 8 ...
Page 374: ...DTX Series CableAnalyzer Technical Reference Handbook B 2 ...