Appendix (continued)
Step Ten
EMPTY CONFIGURATION
This function adjusts the empty linear scaled current output (4mA) and provides two different adjustment
methods:
The primary method involves setting the value based upon the distance from the bottom of the sensor.
This is a measured value using the units of operation for the sensor. For example, if the units of
operation are in meters, then the setting must also be in meters.
A second method involves setting a value based upon the percentage of the
Range
value
.
For
example, if the
Range
is set to 10ft, then a 10% setting is equivalent to 1ft of media height or 9ft of air
gap away from the sensor.
Note: Set the Range value before setting the Empty Configuration value.
Shows the percentage of empty based upon the
Range
setting.
Shows the distance from the bottom of the sensor to the empty tank.
Shows the air gap distance from the media to the bottom of the sensor.
FULL CONFIGURATION
This function adjusts the full linear scaled current output (20mA) and provides two different adjustment
methods:
The primary method involves setting the value based upon the distance from the 0% level setting (see
below). This is a measured value using the units of operation for the sensor. For example, if the units
of operation are in meters, then the setting must also be in meters.
The second method involves setting a value based upon the percentage of the
Range
value
.
For
example, if the
Range
is set to 10ft, then a 95% setting is equivalent to 9.5ft of media height or 0.5ft or
air gap away from the sensor.
Note: Set the Range value before setting the Full configuration value.
Shows the percentage of full based upon the
Range
setting.
Shows the distance from the bottom of the sensor to the full tank.
Shows the air gap distance from the media to the bottom of the sensor.