26
MN301905 Rev A
Install Sensor (continued)
Step Three
SOLIDS INSTALLATION TIPS (CONTINUED)
When using the gimbaled flange, the sensor can easily be mounted to direct the signal energy towards center
of the tank. The angle of the sensor will be dependent on the distance down to the bottom of the tank and the
distance away from the bottom of the cone. Use the chart below to understand the angle required to direct the
signal to the bottom of the cone.
Distance
(Y)
2°
(Z)
4°
(Z)
6°
(Z)
8°
(Z)
10°
(Z)
10’
0.35’ 0.70’
1.05’
1.41’
1.76’
20’
0.70’ 1.40’
2.10’
2.81’
3.53’
30’
1.05’ 2.10’
3.15’
4.22’
5.29’
40’
1.40’ 2.80’
4.20’
5.62’
7.05’
50’
1.75’ 3.50’
5.26’
7.03’
8.82’
60’
2.10’ 4.20’
6.31’
8.43’
10.58’
70’
2.44’ 4.89’
7.26’
9.84’
12.34’
80’
2.79’ 5.59’
8.41’
11.24’ 14.11’
90’
3.14’ 6.29’
9.46’
12.65’ 15.87’
100’
3.49’ 6.99’ 10.51’ 14.05’ 17.63’
Distance
(Y)
2°
(Z)
4°
(Z)
6°
(Z)
8°
(Z)
10°
(Z)
5m
0.17m .35m 0.53m 0.70m 0.88m
10m
0.35m 0.70m 1.05m 1.41m 1.76m
15m
0.52m 1.05m 1.58m 2.11m 2.65m
20m
0.70m 1.40m 2.10m 2.81m 3.53m
25m
0.87m 1.75m 2.63m 3.51m 4.41m
30m
1.05m 2.10m 3.15m 4.22m 5.29m