DOUBLE GLASS - INSTRUCTIONS
The double glass design depends on the blower
’s
ability to move room temperature air from the lower air intake, up between the
internal and external glass, through the chase above the fireplace, and out the upper heat release.
The following sizes MUST be maintained for the upper heat release:
For fireplaces sized
80” & 100”
–
vent area must be at least
200 square inches.
For fireplaces sized
60”
& 70
”
- vent area must be at least
140 square inches
.
For fireplace sized
50”
and below - vent area must be at least
100 square inches.
The following sizes MUST be maintained for the lower air intake:
For fireplaces sized
80
”
& 10
0”
–
vent area must be at least
100 square inches.
For fireplaces sized
60”
& 70
”
- vent area must be at least
70 square inches
.
For fireplaces sized
50”
and below - vent area must be at least
50 square inches.
For See Through and Room Definer fireplaces, the air intake requirements are
double
.
NOTE: Openings above for Heat Release and Air Intake are measured for open air space.
NOTE:
On all
See Through
and
Room Definer
units the air intake must be doubled
To reduce you chase and double glass heat increase your heat release & air intake above listed minimum
The upper heat release may be a single or multiple opening if the total size of all the openings is at least the minimum
requirement listed above. They can be set at the front, back, sides or top.
The lower air intake may be a single or multiple opening if the total size of all the openings is at least the minimum requirement
listed above. They can be set at the front, back, or sides. It is recommended to place one long opening on below the long glass, to
allow for better distribution across all fans of air taken in from the bottom. If implementing side air intakes, make sure side
opening are not farther than 2 feet to the side of the fireplace.
On all
See Through
and
Room Definer
units the air intake must be double, to accommodate fans on either facing.
Lower air intake is REQUIRED for Double Glass and units with an optional blower kit.
POWER REQUIREMENTS
The built-in active blower system for the double glass design requires a power 110v 1PH 15A.
Summary of Contents for Flare Corner Right & Left 30-100"
Page 5: ...5 P a g e SAFETY INFO AND WARNINGS...
Page 9: ...9 P a g e FIREPLACE OPERATION REMOTE CONTROL INSTRUCTIONS...
Page 10: ...10 P a g e...
Page 11: ...11 P a g e...
Page 12: ...12 P a g e...
Page 75: ...75 P a g e EXAMPLES OF HEAT RELEASES...
Page 85: ...85 P a g e ELECTRIC AND CONTROL ELECTRIC DIAGRAM SCREEN Optional 6V power supply and remote...
Page 86: ...86 P a g e DIAGRAM DOUBLE GLASS AND POWER VENT BLUE RECEIVER RELAY GREEN RECEIVER AUX...
Page 88: ...88 P a g e ELECTRIC DIAGRAM PV SYSTEM Ports 49 47 are connected to J6 on fireplace main board...
Page 96: ...96 P a g e Figure 1 Figure 2 Figure 3 Figure 4 Figure 5...
Page 97: ...97 P a g e Figure 6 Figure 7...