Table 2. Available Configurations
TYPE NUMBER
(1)
DESCRIPTION
Bourdon Tube
Sensing Element
Bellows Sensing Element
DESCRIPTION
Sensing Element
(Gauge Pressure
Only)
Gauge
Pressure
Differential
Pressure
Proportional-only controller
4150K
4152K
4154K
Proportional plus reset controller
Without anti-reset windup
4160K
4162K
4164K
Proportional-plus-reset controller
With anti-reset windup
4160KF
4162KF
- - -
Differential gap controller
4150KS
4152KS
- - -
Transmitter
4157K
4158K
4155K
1. The suffix R is added to the type number of a construction specified for reverse action.
Table 3. Bourdon Tube Pressure Ranges and Materials
PRESSURE RANGES
(1)
MAXIMUM ALLOWABLE STATIC PRESSURE
(2)
LIMITS
(3)
PRESSURE RANGES
(1)
Standard
With Optional Travel Stop
(4)
MATERIAL
Psig
Bar
Psig
Bar
Psig
Bar
MATERIAL
0 to 30
0 to 60
0 to 100
0 to 2.0
0 to 4.0
0 to 7.0
30
60
100
2.0
4.0
7.0
48
96
160
3.3
6.6
11
0 to 200
0 to 300
0 to 600
(5)
0 to 1000
(5)
0 to 14
0 to 20
0 to 40
0 to 70
200
300
600
1000
14
20
40
70
280
420
720
1200
19
29
50
83
316 stainless steel
0 to 1500
(5)
0 to 3000
0 to 5000
0 to 100
0 to 200
0 to 350
1500
3000
5000
100
200
350
1650
3300
5500
115
230
380
0 to 8000
0 to 10.000
0 to 550
0 to 700
8000
10,000
550
700
8000
10,000
550
700
1. Range marked on Bourdon tube may be in kPa (1 bar = 100 kPa)
2. This term is defined in ISA Standard S51.1-1979.
3. Bourdon tube may be pressurized to limit shown without permanent zero shift.
4. With travel stop set at 110% of the range.
5. These Bourdon tubes are also available in K-Monel for sour gas service.
Table 4. Bellows Pressure Ranges and Materials
MAXIMUM ALLOWABLE STATIC
PRESSURE
(1)
LIMITS
(2)
PRESSURE RANGES
Brass
Construction
Stainless Steel
Construction
Psig
Bar
Psig
Bar
Vacuum
0 to 60 inch wc (0 to 150 mbar)
0 to 10 inch Hg (0 to 340 mbar)
0 to 30 inch Hg (0 to 1.0 bar)
20
40
40
1.6
2.8
2.8
---
---
100
---
---
6.9
Compound Pressure
30 inch wc vac. to 30 inch wc (75 mbar vac. to 75 mbar)
15 inch Hg vac. to 7.5 psig (500 mbar vac. to 500 mbar)
30 inch Hg vac. to 15 psig (1.0 bar vac. to 1.0 bar)
20
40
40
1.4
2.8
2.8
---
100
100
---
6.9
6.9
Gauge Pressure
Positive pressure
0 to 60 inch wc (0 to 150 mbar)
0 to 100 inch wc
(3)
(0 to 250 mbar)
0 to 140 inch wc
(4)
(0 to 350 mbar)
0 to 5 psig (0 to 0.35 bar)
0 to 7.5 psig (0 to 0.5 bar)
20
20
40
40
40
1.4
1.4
2.8
2.8
2.8
---
---
---
---
---
---
---
---
---
---
Positive ressure
0 to 10 psig (0 to 0.7 bar)
0 to 15 psig (0 to 1.0 bar)
0 to 20 psig (0 to 1.4 bar)
0 to 30 psig (0 to 2.0 bar)
40
40
40
40
2.8
2.8
2.8
2.8
---
100
---
100
---
6.9
---
6.9
Differential Pressure
(5)
0 to 80 inch wc (0 to 300 mbar)
0 to 10 psi (0 to 0.7 bar)
0 to 20 psi (0 to 1.4 bar)
0 to 30 psi (0 to 2.0 bar)
20
40
40
---
1.4
2.8
2.8
---
---
---
---
100
---
---
---
6.9
1. This term is defined in ISA Standard S51.1-1979.
2. Bellows may be pressured to limit shown without permanent zero shift.
3. Type 4158K transmitter only.
4. Except Type 4158K transmitter.
5. The overrange limit for these sensing elements is a differential pressure equal to the maximum allowable static pressure limit.