4150K and 4160K Series
2
Contents (Continued)
Maintenance
20
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing Gauges
20
. . . . . . . . . . . . . . . . . . . . . . . . .
Replacing Bourdon Tube
21
. . . . . . . . . . . . . . . . . . . .
Replacing Bellows Sensing Element
21
. . . . . . . . . .
Changing Proportional or Reset Valve
22
. . . . . . . . .
Changing Anti-Reset Windup Differential
Relief Valve (4160KF)
22
. . . . . . . . . . . . . . . . . . . .
Changing Action
22
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Proportional-Only to a Differential
Gap Controller
22
. . . . . . . . . . . . . . . . . . . . . . . . .
Direct to Reverse Action
22
. . . . . . . . . . . . . . . . . . .
Relay Repair
24
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacement
24
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relay Disassembly
24
. . . . . . . . . . . . . . . . . . . . . . . .
Relay Assembly
25
. . . . . . . . . . . . . . . . . . . . . . . . . .
Changing Output Signal Range
25
. . . . . . . . . . . . . .
Parts Ordering
26
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Kits
26
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controller Repair Kits
26
. . . . . . . . . . . . . . . . . . . . . . .
Relay Repair Kits
26
. . . . . . . . . . . . . . . . . . . . . . . . . .
Relay Replacement Kits
26
. . . . . . . . . . . . . . . . . . . . .
Parts List
26
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Assemblies
26
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Common Parts
26
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relay Assembly
33
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting Parts for Panel, Wall, Pipestand
or Actuator Mounting
33
. . . . . . . . . . . . . . . . . . . . .
Introduction
Scope of Manual
This instruction manual provides installation, operat-
ing, maintenance, and parts information for the 4150K
and 4160K Series Wizard
R
II pressure controllers
and transmitters shown in figure 1. Refer to separate
instruction manuals for information regarding the con-
trol valve, actuator, and accessories.
Only personnel qualified through training or experience
should install, operate, and maintain this instrument. If
there are any questions concerning these instructions,
contact your Fisher sales office or sales representative
before proceeding.
Description
The 4150K and 4160K Series pneumatic pressure
controllers and transmitters use a bellows or Bourdon
tube sensing element to sense the gauge pressure,
vacuum, compound pressure, or differential pressure
of a liquid or gas. The controller or transmitter output
is a pneumatic pressure signal that can be used to
operate a final control element, indicating device, or
recording device.
Specifications
Specifications for the 4150K and 4160K Series con-
trollers and transmitters are listed in table 1. Table 2
explains available configurations and options.
Installation
Standard Installation
The instruments are normally mounted vertical with
the case/cover as shown in figure 1. If installing the
instrument in any other position, be sure that the vent
opening shown in figure 3 is facing downward.
Panel Mounting
Refer to figure 3.
Cut a hole in the panel surface according to the di-
mensions shown in figure 3. Remove the cap screws
(key 252), brackets (key 251), and vent assembly (key
15). Slide the controller or transmitter into the cutout
and reattach the brackets. Tighten the cap screw lo-
cated in the center of each bracket to draw the case
snugly and evenly against the panel. Reinstall the vent
unless a remote vent will be used.