![Fischer Panda Panda 14.000 NE PVK-U Operating Instructions Manual Download Page 49](http://html1.mh-extra.com/html/fischer-panda/panda-14-000-ne-pvk-u/panda-14-000-ne-pvk-u_operating-instructions-manual_2294282049.webp)
Generator Failure
Panda 14.000 NE PVK-U S00420 - Chapter D: Generator Failure Page 45
01. Actuator
02. Spiral thread spindle
03. Regulating nuts max. revolution
04. Spindle nut with rev regulator lever
05. Regulating nuts min. revolution
During any operation at the generator all load have to be switched off to avoid damages at the
equipments. Also the solid state relay, which is installed in the AC-control box must be discon-
nected to avoid an accidentally activation of the booster capacitors.
D.1.4Adjustment of the maximum upper revolution:
1. Disconnect the plug at the electrical supply line of the actuator.
2. Unclamp the countering nut at the limitation screw with a wrench SW 10.
3. Connect an electrical voltage instrument (voltmeter) with a display range until 300V AC to AC
outlet in the electrical cabinet.
4. Be sure that no electrical load is adjusted.
5. Start the generator.
6. Increase the rev of the generator by turning the spindle of the actuator manually until the volt-
meter reach a value of 260V (130V).
7. Turn the limit stop screw tight against the limit stop point at the rev regulator lever.
8. Protect the limit stop screw with the countering nut.
9. Check again if the voltage of the generator is limited to max. 260V (130V) without load.
The adjustment of the upper limitation of the rev serves an additional safety. The value of the
max. voltage lies 5V above the normal operating border.
01. Adjusting screw upper keystroke
02. Countering nut
03. Rev regulator lever
This adjustment should not be chan-
ged, otherwise the warranty expires.
01
02
03
04
05
02
03
01
Summary of Contents for Panda 14.000 NE PVK-U
Page 1: ...Generator type Panda 14 000 NE PVK U 400V 50 Hz 12kW Icemaster Fischer Panda...
Page 28: ...The Panda Generator Page 24 Panda 14 000 NE PVK U S00420 Chapter A The Panda Generator...
Page 62: ...Generator Failure Page 58 Panda 14 000 NE PVK U S00420 Chapter D Generator Failure...
Page 92: ...Appendix Page VIII Panda 14 000 NE PVK U S00420 Chapter F Appendix...
Page 94: ...Measurements Page X Panda 14 000 NE PVK U S00420 Chapter F Appendix F 7 Measurements...
Page 96: ...Wiring diagram control panel Page XII Panda 14 000 NE PVK U S00420 Chapter F Appendix...