Flashover/sparks
in cylinder(only
ELDB)
•
•
Very high water conductivity resulting in
massive electrode burn-off as indicated
by brown-black deposits
Blow-down pump not working properly or
defective
•
•
Deactivate unit immediately
to prevent material damage
Perform maintenance:
- replace electrodes with high
conductivity type
- clean steam cylinder
- check water quality and con-
ductivity (also s. „Intended use“
section)
- optimise blow-down parame-
ters
Consult your expert dealer, if re-
quired
Check blow-down pump func-
tioning and replace pump, if re-
quired. See also
fault
messages
061 to 067 related to
blow-down
Problem
Possible cause for faulty situation
Countermeasure