Page 23
5.2.4 Line-up of the commisioning
parameters
01: Comissioning
No. Parameter
No.
Meaning/Comment
[ ] explains the term in the glossary
min
max
FS
[ ] refers to a related explanation of the term
1 Language
Selection of language
0 German
1 English
2 French
3 Spanish
4 Japanese
5 Italian
6 Russian
2 Date
Set date
3 Time_of_day
Set time
4 Control_settings
Combinations of control type and input signal type/range
0
The selection was carried out separately during initial operation according to
control type, signal type and area. This is a read value only
1
External controller [73] with voltage signal 0... 10 V
2
External control [73] with current signal 0…20 mA
3
External controller [73] with ohmic signal 0...140
Ω
4
Internal PI controller [96], controls with voltage signal 0...10 V
5
Internal PI controller [96], controls with current signal 4... 20 mA
6
Internal PI controller [96], controls with ohmic signal 0...140
Ω
7
1 step operation [44]
8
Control via software control commands [12] through communication
interface [13]
9
Unit operates as slave [94] in a master/slave unit network
11
Selection of current input on the mainboard for the 2nd PI controller when
using the floating max. limiter [35]
12
Selection of voltage input on the 1st relay board for the 2nd PI controller
when using the floating ma. limiter [35]
Pi-controller_V_max_V
PI-controller_4...20 mA
PI-controller_0...140
Ω
1-step
Modbus
Slave
Pi-controller_V_max_mA
Extern_0...20 mA
Extern_0...140
Ω
PI-controller_0...10 V
Castellano
ニホンゴ
Italiano
Русский
DD.MM.YY
HH:MM
Adjustment/value range
Factory setting (FS) Bold
Selection
Deutsch
English
Francais
Selection
User_specified
Extern_0...10 V
Table of commissioning parameters