Table of service parameters
06: Service
No. Parameter
No.
Meaning/Comment
[ ] explains the term in the glossary
min
max
FS
[ ] refers to a related explanation of the term
1 Steam_amount_service
0
65535
4500
Preset steam volume (see [33]) in kg until service message is triggered. For
double cylinder units, this setting applies to both cylinders
4 Service-reset_cyl.
1
Reset steam volume counter for cylinder 1
[33]
0 No
1 Yes
5 Steam_until_msg._cyl.
1
Remaining steam volume for cyl. 1 in kg until service message
[33] is
triggered
7 Service-reset_cyl.
2
Reset steam volume counter for cylinder 2
[33], double cylinder units only
0 No
1 Yes
8 Steam_until_msg._cyl.
2
Remaining steam volume for cyl. 2 in kg until service message
[33] is
triggered
12 Main_contactor
1_reset
Reset K1 counter for main contactor operating cycles
[34]
0 No
1 Yes
13 K1_switching_cycles_until_msg.
Remaining operating cycles for K1 until service message
[34] is triggered
14 Main_contactor
2_reset
Reset K2 counter for main contactor operating cycles
[34]
0 No
1 Yes
15 K2_switching_cycles_until_msg.
Remaining operating cycles for K2 until service message
[34] is triggered
16 Main_contactor
3_reset
Reset K3 counter for. main contactor operating cycles
[34] (double cyl.
units only)
0 No
1 Yes
17 K3_switching_cycles_until_msg.
Remaining operating cycles for K3 until service message
[34] is triggered
18 Main_contactor
4_reset
Reset K4 counter for main contactor operating cycles
[34] (double cyl.
units only)
0 No
1 Yes
19 K4_switching_cycles_until_msg.
Remaining operating cycles for K4 until service message
[34] is triggered
20 Main_contactor
5_reset
Reset K5 counter for main contactor operating cycles
[34] (double cyl.
units only)
0 No
1 Yes
21 K5_switching_cycles_until_msg.
Remaining operating cycles for K5 until service message
[34] is triggered
22 Warning_cyl._full
Warning message about electrode burn-off (only for ELDB [77])
[95]
0 No
message
1
Threshold value 1 for message (lowest sensitivity)
2
Threshold value 2 for message (medium sensitivity)
3
Threshold value 3 for message (highest sensitivity)
23 Warning_pump
Warning message about functional performance of blow-down pump
[95]
24 Warning_valve
Warning message about functional performance of solenoid valves
[95]
Sensitivity 3
Selection
see: 06-22 Warning_cyl._full
Selection
On
Read value
Selection
Off
Sensitivity 1
Sensitivity 2
Selection
Off
On
Read value
Selection
Off
On
Read value
Selection
Off
On
Read value
Selection
Off
On
Read value
Selection
Off
On
Read value
Selection
Off
On
Read value
Adjustment/value range
Factory setting (FS) Bold
Selection
Off
26 Update_function
Status of update function [7]
0
USB stick is not inserted
1
The parameter set which is saved on the stick is loaded
2
The loaded parameter set is checked
3
The parameter set is updated
4
The update was successful
5
USB stick does not contain a parameter set or parameter set is not
compatible
USB-stick_insert
Loading
Checking
Update
Successful
Data_not_valid
see: 06-22 Warning_cyl._full
Read value