5.8.3 Control submenu
Table of control parameters
05: Control
No. Parameter
No.
Meaning/Comment
[ ] explains the term in the glossary
min
max
FS
[ ] refers to a related explanation of the term
1 Control_settings
Combinations of control type and input signal type/range
2 Steam_output_max.
25.0
100.0
100.0
The maximum output power [43] can be limited to between 25 and 100%
3
∆
Power_limitation
0,0
50.0
0.0
Reduction of the maximum steam output for the purpose of load shedding
[101]
4 Output_signal
Mapping of the output signal [69] to an internal value
0 No
mapping
1
Output signal is proportional to the demand [5] from the external controller
[73]
2
Output signal is proportional to the internal actuator signal [42]
3
Output signal is proportional to the actual humidity value [1]
4
Output is used to control a slave [94]
17 Humidity_set_value
0.0
99.0
50.0
Set value [3] of RH [2] in %
18
∆
Set_value_dehumidification
1.0
20.0
10.0
Downstream dehumidifier is actuated if humidity set value has been
exceeded by the respective difference value [%], (PI controller only],
[50]
19
∆
Humidity_ECO
0.0
50.0
10.0
Target humidity is lowered by this percentage when ECO is switched on
20 PI-controller_gain
0.5
100.0
5.0
Proportional part of PI controller
21 PI-controller_integral
0.0
100.0
10.0
Integral part of PI controller
22 Humidity_notification
5.0
99.0
50.0
When the set humidity [%] has been reached, one of the relays is energised,
which must have been assigned code 211 (humidity reached) for this
purpose
23 Humidity_set_max
5.0
99.0
80.0
Specification of max. humidity for the switch-off point when using the floating
max. limiter [35]
24 Pi-controller_max_gain
.5
100.0
5.0
Amplification of 2nd PI controller when using the floating max. limiter [35]
Humidity_actual_value
Control_signal_slave
Selection
see: 01-4 Control_settings
Selection
Off
Control_sig._external
Control_sig._internal
Adjustment/value range
Factory setting (FS) Bold