background image

— 1 —

preface

First of all, thank you for buying a high-performance universal frequency converter!

This is a general high-performance current vector inverter to control the AC asynchronous

motor, which can be used for textile, paper, wire drawing, machine tools, packaging, food, fans,

water pumps and a variety of automated production equipment to drive.

This manual introduces the functional characteristics and use methods of high-performance

general frequency converter, including product selection, parameter setting, operation debugging,

maintenance inspection, etc. Please read this manual carefully before use. The equipment

supporting manufacturer should send this manual to the end user along with the equipment to

facilitate the subsequent use of reference.

matters need attention

To illustrate the detailed part of the product, the legend in this specification is sometimes the status of the

cover or safety cover.

When using this product, be sure to install the shell and cover according to the instructions.

The legend in this instruction are for illustration only and may differ from the product you order.

The company is committed to continuous product improvement, functionality and upgrading, and the
information provided is subject to change without notice.

If you have problems with your use, please contact our regional agents, or contact our customer service
center directly

Summary of Contents for T5R5GB

Page 1: ...ully before use The equipment supporting manufacturer should send this manual to the end user along with the equipment to facilitate the subsequent use of reference matters need attention To illustrat...

Page 2: ...installation hole position of the frequency converter 9 3 2 Wiring 10 Chapter 4 Keyboard Display and Operation 13 4 1 Introduction of the L E D keyboard interface 13 4 2 Description of function code v...

Page 3: ...please do not install it pay attention to Handling should be carried lightly and put gently otherwise there is a danger of damage to the equipment Do not use damaged drives or missing drives there is...

Page 4: ...on the power input terminal R S T and output terminal U V W is correct and check whether the peripheral circuit connected to the driver is fastened otherwise the drive is damaged Any part of the drive...

Page 5: ...drive start and stop otherwise it will cause equipment damage Maintenance danger Do not repair and maintain the equipment with live power otherwise there is a danger of electric shock Cut off the inpu...

Page 6: ...nstration of the type Figure 2 2 Model Description 2 2 Product Series Description Table 2 1 Model and technical data of high performance general frequency converter Frequency converter model Power cap...

Page 7: ...ltage Single phase 3 phase 220V model 200V 240V Three phase 380V model 380V 440V Voltage allowable fluctuation range 15 10 Input power frequency 50Hz or 60Hz with a fluctuation of less than 5 output m...

Page 8: ...MODBUS communication input terminal Five digital input terminals one of which is a high speed pulsed HDI input Two analog quantity input terminals leading out terminal 2 Digital output terminals one...

Page 9: ...Figure 3 2 Outline dimensions of frequency converter product model Installation hole position mm outline dimension mm Installation aperture Net quantity remarks A B H W D mm Kg Single phase 220V S0R4G...

Page 10: ...mensions and Installation Size 3 2 Wiring 3 2 1 standard wiring diagram Figure 3 3 Standard wiring diagram K2 relay is not installed by default and can be selected according to customer requirements 3...

Page 11: ...op terminal of the three phase frequency converter Terminal mark name explain R S T Three phase power supply input terminal AC input three phase power connection point Positive and negative DC bus ter...

Page 12: ...e voltage current is selected by the 06 10 menu 2 Input impedance voltage input impedance 20K current input impedance 510 AI2 GND Analog quantity input terminal 2 figure import X1 COM Digital input 1...

Page 13: ...the following figure Figure 4 1 Schematic diagram of the operation panel 1 Function indicator light instructions RUN when the lamp is out the converter is down and when the lamp is on the converter is...

Page 14: ...shutdown and running display interface select the display parameter when modifying the parameter select the parameter RUN Run the key In keyboard operation mode used for running operations STOP RES ET...

Page 15: ...stant torque load 1 P type fan water pump type load 0 00 01 Motor control mode 0 Keep 1 No speed sensor vector control 2 with torque control 2 V F control 2 00 02 Run the command source selection 0 Ke...

Page 16: ...requen cy 00 09 630 00Hz 50 00Hz 00 12 upper limiting frequency 00 10 00 08 50 00Hz 00 14 Lower limit frequency 0 00Hz 00 09 0 00Hz 00 15 carrier frequency 1 0 15 0K Hz Model determination 00 16 Zero...

Page 17: ...tor resistance 0 001 65 535 Model determination 01 09 Motor leakage resistance 0 1 6553 5mH Model determination 01 10 Motor mutual resistance 0 1 6553 5mH Model determination 01 11 No load current of...

Page 18: ...inimum voltage V1 0 0 V2 0 0 02 09 V F transition compensation gain 0 0 200 0 100 0 02 10 The V F low frequency oscillatory suppression coefficient 0 100 10 02 11 V F high frequency oscillation suppre...

Page 19: ...ation voltage number setting 0 0 100 0 0 0 02 18 V F separation voltage acceleration time 0 0 3600 0s 0 0s 02 19 V F separation voltage deceleration time 0 0 3600 0s 0 0s 02 20 V F separation voltage...

Page 20: ...in 50 200 100 03 09 The ACR current loop K P 0 65535 1000 03 10 The ACR current loop K I 0 65535 1000 03 11 Vector 2 constant power weak magnetic constant 0 1 2 0 0 3 03 12 Constant power minimum weak...

Page 21: ...mber setting 04 05 and 04 06 1 AI1 2 AI2 3 AI3 4 HDI 5 Multi section speed 6 RS 485 communication 7 Keyboard analog potentiometer 0 04 04 Reverse torque ceiling frequency source ditto 0 04 05 Forward...

Page 22: ...then start it 2 Speed tracking to start 0 05 01 Start frequency 0 00 50 00Hz 0 50Hz 05 02 Startup frequency retention time 00 0 50 0s 0 0s 05 03 Start the DC brake current 0 0 100 0 0 0 05 4 Start the...

Page 23: ...e by speed 1 05 20 Feedback speed detection time 0 00 100 00s 0 05s 05 21 Start delay 0 0 60 0s 0 0s 05 22 Stop speed delay 0 0 100 0s 0 0s 05 23 Brake unit action 0 Disable 1 enabled 1 05 24 Brake un...

Page 24: ...ontrol is paused 26 Suspension pause stop at current frequency 27 Swing frequency reset back to center frequency 28 Counter reset 29 Torque speed control switch 30 Prohibition acceleration and deceler...

Page 25: ...s 06 16 X2 terminal opening delay 0 00 50 000s 0 000s 06 17 The X2 terminal will disconnect the delay 0 00 50 000s 0 000s 06 18 X3 terminal opening delay 0 00 50 000s 0 000s 06 19 The X3 terminal will...

Page 26: ...ve operation shutdown instruction clearance 06 35 UP terminal frequency change rate 0 01 50 00H z s 0 50H z s 06 36 Rate of change in DOWN terminal frequency 0 01 50 00H z s 0 50H z s 06 37 HDI input...

Page 27: ...54 0 00V 06 53 The lower limit of AI3 is set accordingly 100 0 100 0 0 0 06 56 AI3 upper limit 06 54 10 00V 10 00V 06 57 The upper limit of AI3 is set accordingly 100 0 100 0 100 0 06 58 AI3 input fil...

Page 28: ...virtual terminal output 07 02 HDO terminal output function selection 0 07 03 K 1 relay output function selection 1 07 04 K 2 relay output function selection 5 07 05 AO1 output function selection 0 Ru...

Page 29: ...t limit limit 0 00 50 00K Hz 50 00K Hz 07 22 HDO output filtering time 0 000s 10 000s 0 000s 07 23 Y1 opening delay 0 00 50 000s 0 000s 07 24 Y1 disconnection delay 0 00 50 000s 0 000s 07 25 HDO openi...

Page 30: ...id for the panel controls 1 Effective for both panel and terminal control 2 Effective for both panel and communication control 3 Effective for all control modes 0 08 04 Restore factory parameters 0 No...

Page 31: ...drops 1 Zero zero when the power is dropped 00 08 08 Function code parameter replication 0 No operation 1 Function parameters are uploaded to the keyboard 2 Download the keyboard function parameters...

Page 32: ...inverter overload percentage bright BIT6 ramp frequency given value Hz bright BIT7 Line speed BIT8 AC incoming line current BIT 9 Upper limit frequency 0000 08 11 LED shutdown display parameters 0000...

Page 33: ...ork factor display coefficient 0 00 1 00 0 56 08 19 Cumulative running time 0 65535h 08 20 Monitor the high cumulative power consumption Cumulative power consumption 08 20 1000 08 21 0K Wh 08 21 Monit...

Page 34: ...voltage 48 Electronic overload failure 6 Slow down over voltage 51 The initial position is dysregulated 7 Constant speed overvoltage 60 Brake pipe protection 8 9 The bus is under pressure 10 Frequency...

Page 35: ...Operating frequency of the previous failure 09 15 Given the frequency of the previous fault slope 09 16 The previous fault output voltage 09 17 Previous fault output current 09 18 Previous fault bus...

Page 36: ...alid 1 valid 1 10 03 Over voltage stall action voltage The 220V model 120 150 120 The 380V model 120 150 140 10 04 Overflow protection options Individual bit Overcurrent protection enables 0 Invalid 1...

Page 37: ...ncy converter overload warning shutdown after overload 2 The frequency converter has overload warning and continue to run and stop after underload 3 Stop ter stops after underload Hundred under overlo...

Page 38: ...nstantaneous power outage operation 0 Do not continue to operate 1 Keep running 0 10 20 Insient power outage and operation waiting time 0 0 3600 0s 1 0s 10 21 Insient power drop and frequency drop ena...

Page 39: ...lower than Lower limit frequency operating mode 0 Run at the lower limit frequency 1 Downtime 2 Sleep 0 11 10 Sleep recovery delay 0 0 3600 0s 0 0s 11 11 Drop frequency 0 00 10 00Hz 0 00Hz 11 12 Heat...

Page 40: ...ency check value 0 00 P00 03 50 00Hz 11 33 The FDT1 frequency detection lag value 0 0 100 0 5 0 11 34 FDT2 frequency check value 0 00 Maximum frequency 50 00Hz 11 35 The FDT2 frequency check lag value...

Page 41: ...1 AI2 2 AI3 3 HDI 4 RS 485 communication 5 Keyboard analog potentiometer 0 12 03 PID application direction 0 Positive effect 1 Counteraction 0 12 04 Proportional gain of K P1 0 00 100 00 1 00 12 05 In...

Page 42: ...the upper and lower limits decade 0 Consistent with the set direction 1 Opposite to the set direction hundreds place 0 Reference to the maximum frequency limit 1 Reference frequency source A limit ki...

Page 43: ...value 100 0 100 0 0 0 13 07 Multistage speed 7 frequency setting value 100 0 100 0 0 0 13 08 Multiple segment speed 8 frequency setting value 100 0 100 0 0 0 13 09 Multistage speed 9 frequency Setpoin...

Page 44: ...LC segment 4 runtime 0 0 6553 5 s min 0 0s min 13 21 PLC segment 5 runtime 0 0 6553 5 s min 0 0s min 13 22 PLC segment 6 runtime 0 0 6553 5 s min 0 0s min 13 23 PLC segment 7 runtime 0 0 6553 5 s min...

Page 45: ...7 B it14 15 two bit values selected acceleration and deceleration time 1 2 3 4 0000 13 33 PLC periods 8 to 15 Value range 0x0000 0xFFFF Paragraph 8 B it0 1 two bit values selected acceleration and dec...

Page 46: ...otentiometer 7 The preset frequency can be fine tuned 0 14 Groups of SCI communication parameters 14 00 Address of this machine 0 Broadcast address 1 247 1 14 01 Communication Porter rate 0 1200BPS 1...

Page 47: ...0 FC name Minimum unit Address Address HEX Address Address DEC 30 Groups of monitoring parameters 30 00 running frequency 0 01H z 0x7000 28672 30 01 Set the frequency 0 01H z 0x7001 28673 30 02 busbar...

Page 48: ...converter rated voltage 1V 0x7016 28694 30 23 Power converter rated current 0 1A 0x7017 28695 30 24 linear velocity 1m Min 0x7018 28696 30 25 This operation time 1Min 0x7019 28697 30 26 The slope give...

Page 49: ...tor wire or motor to ensure its normal operation Err02 OC1 Accelerate over current 1 There is ground or short circuit 2 The control mode is a vector and has no parameter identification 3 Acceleration...

Page 50: ...l the brake unit and the resistance Err07 Ov3 Constant speed overvoltage 1 High input voltage 2 There is external forces dragging the motor during operation 1 Adjust the voltage to the normal range 2...

Page 51: ...g to remove the faulty operation Err16 CE 485 Communication fault 1 The upper position computer does not work normally 2 The communication line is abnormal 3 Communication parameter group is not set c...

Page 52: ...3 Overload or blocked rotation 1 Motor parameter identification 2 Speed deviation detection parameters are reasonably reset 3 Check the load to ensure that the load is normal Err 48 oL3 Electronic ov...

Page 53: ...485 asynchronous half duplex The RS485 terminal default data format is detailed in the SCI group parameters A 2 Communication mode 1 Frequency converter is a slave the main and slave peer to point com...

Page 54: ...tiple registers 0x06 Write a single register to the frequency converter 0x10 Write multiple registers to the frequency converter data It mainly includes register address register number and register c...

Page 55: ...urn to 0x1388 5000 or 50 00H z A 4 2 Command code 0x06 Write a single register ask PDU device address 1 Bytes 0x01 command code 1 Bytes 0x06 start address Two bytes 0x0000 0xFFFF high 8 bit address at...

Page 56: ...Bytes 0x10 start address Two bytes 0x0000 0xFFFF high 8 bit address at first Number of registers Two bytes 0x0001 0x0010 1 16 high 8 bits in front CRC check code Two bytes CRC low 8 in the anterior a...

Page 57: ...int16 data Uint16 len Uint16 crcValue 0xffff Uint16 i while len crcValue data for i 0 i 7 i if crcValue 0x0001 crcValue crcValue 1 0xa001 else crcValue crcValue 1 return crcValue A 7 Register address...

Page 58: ...00 00 100 00 negative motor reversal 0x 1001 running frequency 0x 1002 busbar voltage 0x 1003 output voltage 0x 1004 output 0x 1005 output power 0x 1006 output torque 0x 1007 running speed 0x 1008 DI...

Page 59: ...0008 Stop parking 0x2001 Output terminal function value 23 Bit0 Y1 Bit1 HDO Bit2 R 1 Bit3 R 2 14 07 0 DO output terminal control 14 07 1 the communication setting frequency 0 Fmax in unit 0 01Hz 0x200...

Page 60: ...rotected fault code please read the Group 09 Fault Record Parameters A 8 Communication error response Communication error code list error code name description 0x01 The command code is illegal The com...

Page 61: ...x80 to 0x83 0x 86 0x06 Write error When 0x06 When an error writes a command the command code in the responding data frame changes from 0x06 0x80 to 0x86 0x 90 0x 10 Read error When the responding data...

Page 62: ...ro 00 03 7 PID control 06 59 10 06 60 1 Pressure sensor supply voltage 10V 20 00 10 16 kg 20 01 5 Target pressure 20 02 5 dormant pressure 20 03 3 wake up pressure 20 04 0 05 stable pressure deviation...

Page 63: ...ters and secondary disasters C Hardware damage caused by artificial fall and transportation after the purchase D Damage caused by not following the user manual provided by our company E Failure and da...

Page 64: ...ormance Universal Converter User Manual 64 Product Warranty Card customer information Address Unit name Postal Code contacts contact number on product information product model Body barcode paste here...