Suggested Specifications for a Programming Flame Safeguard for Automatically Ignited Oil or Gas
or Combination Fuel Burners.
1.
Each burner shall be equipped with an electronic programing flame safeguard control that is
approved by UL, FM, CSA.
2.
The programming sequence shall be completely controlled by solid state timing logic. The pro-
grammer shall be a plug-in module.
3.
The control shall provide direct connection of limit and operating controls. Fuel valve interlock,
low fire start interlock, running interlocks such as air flow, fuel pressure and temperature and
Burner Motor, Ignition, Main fuel valves and lockout alarm.
4.
Operational test facilities shall be provided for measuring flame signal strength and line and load
voltages.
5.
The control shall be a plug-in design.
6.
Plug-in solid state flame amplifiers shall be provided for the rectification, Infrared
(AUTOCHECK), Ultraviolet or ultraviolet repetitive self-check flame detection.
7.
The burner management controls shall be Fireye series D-30.