2
£
SPECIFICATIONS
Supply Voltage:
120V (Max. 132V, Min. 102V) 50/60 Hz.
Power Consumption:
Operating 20VA
Maximum simultaneous connected load:
2000VA
Humidity:
85% RH max. Non-Condensing
APPROVALS
Underwriters Laboratories Inc.
Listed: Guide MCCZ, File Mp1537
Underwriters Laboratories, Inc.
Recognized: Guide MCCZ2, File MP1537
Canadian Standards Association:
Certified: LR7989
Factory Mutual System:
Approved: Report (J.I.) 1C1A1.AF
Three LED lights on the Fireye chassis provide the following indication:
•
Air Flow — lights when interlock circuit is closed.
•
TFI — lights during pilot trial-for-ignition period.
•
Fireye — lights when flame is detected.
OPERATING TEMPERATURE LIMITS:
PRODUCT
MAX.
MIN.
Control-Amplifier-Programmer
140
q
F (60
q
C)
- 40
q
F/C
UV1A, UV2, UV8A, UV90 Scanner
200
q
F (93
q
C)
- 40
q
F/C
45UV5 Scanner
200
q
F (93
q
C)
- 40
q
F/C
48PT2 Scanner
140
q
F (60
q
C)
- 40
q
F/C
69ND1 Flame Rod (TIP 2460
q
F)
1500
q
F (816
q
C)
- 40
q
F/C
Humidity 85% RH MAX. NON-Condensing
MAXIMUM LOAD RATING FOR SERIES D30 CONTROLS
Terminal
Typical Load
A
Maximum Rating @120V -60Hz
B
Alternate Rating @120V -60Hz
X, 5, 6
(Individually or
Combined)
Pilot Valve(s) and
Ignition Transformers
50VA Pilot Duty (solenoid valves) plus
500VA (Transformer)
125VA Pilot Duty (solenoid valve) plus
250VA (Transformer)
7
Main Fuel Valve(s)
250VA Pilot Duty (Solenoid Valve)
1250VA Opening. 500VA holding
(Motorized Valve) plus 65VA Pilot
Duty (solenoid valve)
M
Burner/Blower Motor
9.8 F.L.A.
58.8 L.R.A.
250VA Pilot Duty
(motor starter coil)
A
Alarm
50VA Pilot Duty
Terminal ratings may be selected from either column A or B:
(selecting the rating from the column for each terminal which best applies to the connected load on that terminal).